Rexroth IndraDrive
Command Diagnostic Messages
9-5
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
C07_2 Load def. proc. com. (load def. pr. for safety techn.)
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
The C07_2 message on the display of the drive controller shows that the
C07_2 Load def. proc. com. (load def. pr. for safety techn.)
command
was activated.
The command can be started as follows:
1. Enter value 165 for "load defaults procedure for safety technology" in
parameter
P-0-4090, Index for C07 Load defaults procedure
2. Start
S-0-0262, C07_x Load defaults procedure command
Note:
It is possible to start further commands with parameter
S-0-0262. In parameter
P-0-4090, Index for C07 Load
defaults procedure
it is possible to set which commands is
started.
The command
C07_2 Load def. proc. com. (load def. pr. for safety
techn.)
deactivates the safety technology and sets all safety technology
parameters to their default value.
CAUTION
The command C07_2 Load def. proc. com. (load
def. pr. for safety techn.) overwrites user-
defined safety technology settings!
⇒
Only use this command if you want to commission
safety technology again.
C0720 - Attributes
Display:
C07_2
Mess. no.:
C0720 (hex)