156
[1.7 APPLICATION FUNCT.]
(FUn-)
(1) The parameter can also be accessed in the
[1.3 SETTINGS]
(SEt-)
menu.
(2) In corresponds to the rated drive current indicated in the Installation Manual and on the drive nameplate.
Code
Name/Description
Adjustment range
Factory setting
CLI-
•
[2nd CURRENT LIMIT.]
LC2
• [Current limit 2]
[No]
(nO)
nO
LI1
-
-
-
-
[No]
(nO)
: Function inactive.
-
[LI1]
(LI1)
:
:
-
[...]
(...)
: See the assignment conditions on page
109
.
If the assigned input or bit is at 0, the first current limitation is active.
If the assigned input or bit is at 1, the second current limitation is active.
CL2
• [I Limit. 2 value]
(1)
0 to 1.1 or 1.2 In (2)
according to rating
1.1 or 1.2 In (2)
according to rating
Second current limitation The parameter can be accessed if
[Current limit 2]
(LC2)
is not
[No]
(nO)
.
Note: If the setting is less than 0.25 In, the drive may lock in
[Output Phase Loss]
(OPF)
fault mode
if this has been enabled (see page
178
). If it is less than the no-load motor current, the limitation no
longer has any effect.
CLI
• [Current Limitation]
(1)
0 to 1.1 or 1.2 In (2)
according to rating
1.1 or 1.2 In (2)
according to rating
First current limitation
Note: If the setting is less than 0.25 In, the drive may lock in
[Output Phase Loss]
(OPF)
fault mode
if this has been enabled (see page
178
). If it is less than the no-load motor current, the limitation no
longer has any effect.
Parameter that can be modified during operation or when stopped.