138
[1.7 APPLICATION FUNCT.]
(FUn-)
(1) The parameter can also be accessed in the
[1.3 SETTINGS]
(SEt-)
menu.
Code
Name/Description
Adjustment range
Factory setting
FLI-
•
[FLUXING BY LI]
FLU
• [Motor fluxing]
(1)
[No]
(FnO)
FnC
FCt
FnO
-
[Not cont.]
(FnC)
: Non-continuous mode
-
[Continuous]
(FCt)
: Continuous mode. This option is not possible if
[Auto DC injection]
(AdC)
page
127
is
[Yes]
(YES)
or if
[Type of stop]
(Stt)
page
125
is
[Freewheel]
(nSt)
.
-
[No]
(FnO)
: Function inactive
At and above 90 kW for ER40-.../4K/G, if
[Motor control type]
(Ctt)
page
64
=
[SVC V]
(UUC)
or
[Energy
Sav.]
(nLd)
, this selection cannot be made and the factory setting is replaced by
[Not cont.]
(FnC)
.
If
[Motor control type]
(Ctt)
=
[Sync. mot.]
(SYn)
the factory setting is replaced by
[Not cont.]
(FnC)
.
In order to obtain rapid high torque on startup, magnetic flux needs to already have been established in
the motor.
• In
[Continuous]
(FCt)
mode, the drive automatically builds up flux when it is powered up.
• In
[Not cont.]
(FnC)
mode, fluxing occurs when the motor starts up.
The flux current is greater than nCr (configured rated motor current) when the flux is established and is then
adjusted to the motor magnetizing current...
If
[Motor control type]
(Ctt)
page
64
=
[Sync. mot.]
(SYn)
, the
[Motor fluxing]
(FLU)
parameter causes the
alignment of the motor and not the fluxing.
FLI
• [Fluxing assignment]
[No]
(nO)
nO
LI1
-
-
-
-
[No]
(nO)
: Function inactive
-
[LI1]
(LI1)
:
:
-
[...]
(...)
: See the assignment conditions on page
109
.
Assignment is only possible if
[Motor fluxing]
(FLU)
is not
[Continuous]
(FCt)
.
• In
[Not cont.]
(FnC)
mode:
- If an LI or a bit is assigned to the motor fluxing command, flux is built up when the assigned input or bit
is at 1.
- If an LI or a bit has not been assigned, or if the LI or bit assigned is at 0 when a run command is sent,
fluxing occurs when the motor starts.
• In
[No]
(FnO)
mode:
- If an LI or a bit is assigned to the motor fluxing command, flux is built up when the assigned input or bit
is at 1 and is suppressed when the assigned input or bit is at 0.
Parameter that can be modified during operation or when stopped.
CAUTION
Check that the motor will withstand this current without overheating.
Failure to follow these instructions can result in equipment damage.