[1.8 FAULT MANAGEMENT]
(FLt-)
Code
Name/Description
Adjustment range
Factory setting
Atr-
•
[AUTOMATIC RESTART]
Atr
• [Automatic restart]
[No]
(nO)
nO
YES
-
[No]
(nO)
: Function inactive
-
[Yes]
(YES)
: Automatic restart, after locking on a fault, if the fault has disappeared and the other
operating conditions permit the restart. The restart is performed by a series of automatic attempts
separated by increasingly longer waiting periods: 1 s, 5 s, 10 s, then 1 mn for the following attempts.
The drive fault relay remains activated if this function is active. The speed reference and the operating
direction must be maintained.
Use 2-wire control (
[2/3 wire control]
(tCC)
=
[2 wire]
(2C)
and
[2 wire type]
(tCt)
=
[Level]
(LEL)
see page
77
).
If the restart has not taken place once the configurable time tAr has elapsed, the procedure is aborted and
the drive remains locked until it is turned off and then on again.
The faults which permit this function are listed on page
222
:
tAr
• [Max. restart time]
[5 minutes]
(5)
5
10
30
1h
2h
3h
Ct
-
[5 minutes]
(5)
: 5 minutes
-
[10 minutes]
(10)
: 10 minutes
-
[30 minutes]
(30)
: 30 minutes
-
[1 hour]
(1h)
: 1 hour
-
[2 hours]
(2h)
: 2 hours
-
[3 hours]
(3h)
: 3 hours
-
[Unlimited]
(Ct)
: Unlimited
Max. duration of restart attempts. This parameter appears if
[Automatic restart]
(Atr)
=
[Yes]
(YES)
.
It can be used to limit the number of consecutive restarts on a recurrent fault.
WARNING
UNINTENDED EQUIPMENT OPERATION
Check that an automatic restart will not endanger personnel or equipment in any way.
Failure to follow these instructions can result in death or serious injury.