111
[1.6 COMMAND]
(CtL-)
Code
Name/Description
Adjustment range
Factory setting
CCS
• [Cmd switching]
[ch1 active]
(Cd1)
Cd1
Cd2
LI1
-
-
-
The parameter can be accessed if
[Profile]
(CHCF)
=
[Separate]
(SEP)
or
[I/O profile]
(IO)
-
[ch1 active]
(Cd1)
:
[Cmd channel 1]
(Cd1)
active (no switching)
-
[ch2 active]
(Cd2)
:
[Cmd channel 2]
(Cd2)
active (no switching)
-
[LI1]
(LI1)
:
:
-
[...]
(...)
: See the assignment conditions on page
109
(not CDOO to CD14).
If the assigned input or bit is at 0, channel
[Cmd channel 1]
(Cd1)
is active.
If the assigned input or bit is at 1, channel
[Cmd channel 2]
(Cd2)
is active.
Cd1
• [Cmd channel 1]
[Terminals]
(tEr)
tEr
LCC
Mdb
CAn
nEt
APP
-
[Terminals]
(tEr)
: Terminals
-
[HMI]
(LCC)
: Graphic display terminal
-
[Modbus]
(Mdb)
: Integrated Modbus
-
[CANopen]
(CAn)
: Integrated CANopen
-
[Com. card]
(nEt)
: Communication card (if inserted)
-
[Prog. card]
(APP)
: Controller Inside card (if inserted)
The parameter is available if
[Profile]
(CHCF)
=
[Separate]
(SEP)
or
[I/O profile]
(IO)
.
Cd2
• [Cmd channel 2]
[Modbus]
(Mdb)
tEr
LCC
Mdb
CAn
nEt
APP
-
[Terminals]
(tEr)
: Terminals
-
[HMI]
(LCC)
: Graphic display terminal
-
[Modbus]
(Mdb)
: Integrated Modbus
-
[CANopen]
(CAn)
: Integrated CANopen
-
[Com. card]
(nEt)
: Communication card (if inserted)
-
[Prog. card]
(APP)
: Controller Inside card (if inserted)
The parameter is available if
[Profile]
(CHCF)
=
[Separate]
(SEP)
or
[I/O profile]
(IO)
.
rFC
• [Ref. 2 switching]
[ch1 active]
(Fr1)
Fr1
Fr2
LI1
-
-
-
-
[ch1 active]
(Fr1)
: No switching,
[Ref.1 channel]
(Fr1)
active
-
[ch2 active]
(Fr2)
: No switching,
[Ref.2 channel]
(Fr2)
active
-
[LI1]
(LI1)
:
:
-
[...]
(...)
: See the assignment conditions on page
109
(not CDOO to CD14).
If the assigned input or bit is at 0, channel
[Ref.1 channel]
(Fr1)
is active.
If the assigned bit or input is at 1, channel
[Ref.2 channel]
(Fr2)
is active.
Fr2
• [Ref.2 channel]
[No]
(nO)
nO
AI1
AI2
AI3
AI4
UPdt
LCC
Mdb
CAn
nEt
APP
PI
PG
-
[No]
(nO)
: Not assigned If
[Profile]
(CHCF)
=
[Not separ.]
(SIM)
, command is at the terminals with
a zero reference. If
[Profile]
(CHCF)
=
[Separate]
(SEP)
or
[I/O profile]
(IO)
, the reference is zero.
-
[AI1]
(AI1)
: Analog input
-
[AI2]
(AI2)
: Analog input
-
[AI3]
(AI3)
: Analog input, if ER40 extension card "In-/Out extension" has been inserted
-
[AI4]
(AI4)
: Analog input, if ER40 extension card "In-/Out extension" has been inserted
-
[+/- Speed]
(UPdt)
: +/-Speed command
-
[HMI]
(LCC)
: Graphic display terminal
-
[Modbus]
(Mdb)
: Integrated Modbus
-
[CANopen]
(CAn)
: Integrated CANopen
-
[Com. card]
(nEt)
: Communication card (if inserted)
-
[Prog. card]
(APP)
: Controller Inside card (if inserted)
-
[RP]
(PI)
: Frequency input, if ER40 extension card "In-/Out extension" has been inserted
-
[Encoder]
(PG)
: Encoder input, if encoder card has been inserted
Содержание ER40-G
Страница 2: ......
Страница 21: ...21 The display flashes to indicate the presence of a fault ...
Страница 241: ......