164
[1.7 APPLICATION FUNCT.]
(FUn-)
Motor or configuration switching
[MULTIMOTORS/CONFIG.]
The drive may contain up to 3 configurations, which can be saved using the
[1.12 FACTORY SETTINGS]
(FCS-)
menu, page
201
.
Each of these configurations can be activated remotely, enabling adaptation to:
• 2 or 3 different motors or mechanisms (multimotor mode)
• 2 or 3 different configurations for a single motor (multiconfiguration mode)
The two switching modes cannot be combined.
Note: The following conditions MUST be observed:
• Switching may only take place when stopped (drive locked). If a switching request is sent during operation, it will not be executed
until the next stop.
• In the event of motor switching, the following additional conditions apply:
- When the motors are switched, the power and control terminals concerned must also be switched as appropriate.
- The maximum power of the drive must not be exceeded by any of the motors.
• All the configurations to be switched must be set and saved in advance in the same hardware configuration, this being the
definitive configuration (option and communication cards). Failure to follow this instruction can cause the drive to lock on
an
[Incorrect config.]
(CFF)
fault.
Menu and parameters switched in multimotor mode
•
[1.3 SETTINGS]
(SEt-)
•
[1.4 MOTOR CONTROL]
(drC-)
•
[1.5 INPUTS / OUTPUTS CFG]
(I-O-)
•
[1.6 COMMAND]
(CtL-)
•
[1.7 APPLICATION FUNCT.]
(FUn-)
with the exception of the
[MULTIMOTORS/CONFIG.]
function (to be configured once only)
•
[1.8 FAULT MANAGEMENT]
(FLt)
•
[1.13 USER MENU]
•
[USER CONFIG.]
: The name of the configuration specified by the user in the
[1.12 FACTORY SETTINGS]
(FCS-)
menu
Menu and parameters switched in multiconfiguration mode
As in multimotor mode, except for the motor parameters that are common to the three configurations:
- Rated current
- Thermal current
- Rated voltage
- Rated frequency
- Rated speed
- Rated power
- Magnetizing current at zero frequency
- IR compensation
- Slip compensation
- Synchronous motor parameters
- Type of thermal protection
- Thermal state
- The auto-tuning parameters and motor parameters that can be accessed in expert mode
- Type of motor control
Note: No other menus or parameters can be switched.