86
[1.5 INPUTS / OUTPUTS CFG]
(I-O-)
Code
Name/Description
Adjustment range
Factory setting
AI4-
•
[AI4 CONFIGURATION]
Can be accessed if an ER40 option card "In-/Out- extension" has been inserted
AI4A
• [AI4 assignment]
Read-only parameter, cannot be configured.
It displays all the functions associated with input AI4 in order to check, for example, for compatibility
problems.
AI4t
• [AI4 Type]
[Voltage]
(10U)
10U
0A
-
[Voltage]
(10U)
: Voltage input
-
[Current]
(0 A)
: Current input
CrL4
• [AI4 min value]
0 to 20.0 mA
0 mA
The parameter can be accessed if
[AI4 Type]
(AI4t)
=
[Current]
(0 A)
UIL4
• [AI4 min value]
0 to 10.0 V
0 V
The parameter can be accessed if
[AI4 Type]
(AI4t)
=
[Voltage]
(10U)
CrH4
• [AI4 max value]
0 to 20.0 mA
20.0 mA
The parameter can be accessed if
[AI4 Type]
(AI4t)
=
[Current]
(0 A)
UIH4
• [AI4 max value]
0 to 10.0 V
10.0 V
The parameter can be accessed if
[AI4 Type]
(AI4t)
=
[Voltage]
(10U)
AI4F
• [AI4 filter]
0 to 10.00 s
0 s
Interference filtering.
AI4L
• [AI4 range]
[0 – 100%]
(POS)
POS
nEG
-
[0 – 100%]
(POS)
: Unidirectional input
-
[+/- 100%]
(nEG)
: Bidirectional input
Example: On a 0/10 V input
- 0 V corresponds to reference -100%
- 5 V corresponds to reference 0%
- 10 V corresponds to ref100%
AI4E
• [AI4 Interm.point X]
0 to 100%
0%
Input delinearization point coordinate.
• 0% corresponds to
[Min value]
if the range is 0
...
100%.
• 0% corresponds to
if the range is -100%
...
+ 100%.
• 100% corresponds to
[Max value]
.
AI4S
• [AI4 Interm.point Y]
0 to 100%
0%
Output delinearization point coordinate (frequency reference).
[Max value]
+
[Min value]