125
[1.7 APPLICATION FUNCT.]
(FUn-)
(1) The parameter can also be accessed in the
[1.3 SETTINGS]
(SEt-)
menu.
Code
Name/Description
Adjustment range
Factory setting
Stt-
•
[STOP CONFIGURATION]
Note: Some types of stop cannot be used with all other functions. Follow the instructions on
page
115
.
Stt
• [Type of stop]
[Ramp stop]
(rMP)
rMP
FSt
nSt
dCI
Stop mode on disappearance of the run command or appearance of a stop command.
-
[Ramp stop]
(rMP)
: On ramp
-
[Fast stop]
(FSt)
: Fast stop
-
[Freewheel]
(nSt)
: Freewheel stop This selection will not appear if
[Motor fluxing]
(FLU)
page
138
=
[Continuous]
(FCt)
.
-
[DC injection]
(dCI)
: DC injection stop
If the
[Low speed time out]
(tLS)
parameter page
53
or
150
is not 0,
[Type of stop]
(Stt)
is forced to
[Ramp stop]
(rMP)
.
nSt
• [Freewheel stop ass.]
[No]
(nO)
nO
LI1
-
-
C101
-
-
-
Cd00
-
-
[No]
(nO)
: Not assigned
-
[LI1]
(LI1)
to
[LI6]
(LI6)
-
[LI7]
(LI7)
to
[LI10]
(LI10)
: If VW3A3201 logic I/O card has been inserted
-
[LI11]
(LI11)
to
[LI14]
(LI14)
: If VW3A3202 extended I/O card has been inserted
-
[C101]
(C101)
to
[C115]
(C115)
: With integrated Modbus in [I/O profile] (IO)
-
[C201]
(C201)
to
[C215]
(C215)
: With integrated CANopen in [I/O profile] (IO)
-
[C301]
(C301)
to
[C315]
(C315)
: With a communication card in [I/O profile] (IO)
-
[C401]
(C401)
to
[C415]
(C415)
: With a Controller Inside card in [I/O profile] (IO)
-
[CD00]
(Cd00)
to
[CD13]
(Cd13)
: In [I/O profile] (IO) can be switched with possible logic inputs
-
[CD14]
(Cd14)
to
[CD15]
(Cd15)
: In [I/O profile] (IO) can be switched without logic inputs
The stop is activated when the input or bit is at 0. If the input returns to state 1 and the run command is
still active, the motor will only restart if
[2/3 wire control]
(tCC)
page
77
=
[2 wire]
(2C)
and
[2 wire type]
(tCt)
=
[Level]
(LEL)
or
[Fwd priority]
(PFO)
. If not, a new run command must be sent.
FSt
• [Fast stop assign.]
[No]
(nO)
nO
LI1
-
-
-
Note: This function cannot be used with certain other functions. Follow the instructions on
page
115
.
-
[No]
(nO)
: Not assigned
-
[LI1]
(LI1)
:
:
-
[...]
(...)
: See the assignment conditions on page
109
.
The stop is activated when the input changes to 0 or the bit changes to 1(bit in [I/O profile] (IO) at 0).
If the input returns to state 1 and the run command is still active, the motor will only restart if
[2/3 wire
control]
(tCC)
page
77
=
[2 wire]
(2C)
and
[2 wire type]
(tCt)
=
[Level]
(LEL)
or
[Fwd priority]
(PFO)
.
If not, a new run command must be sent.
dCF
• [Ramp divider]
(1)
0 to 10
4
The parameter can be accessed if
[Type of stop]
(Stt)
=
[Fast stop]
(FSt)
and if
[Fast stop assign.]
(FSt)
is not
[No]
(nO)
.
The ramp that is enabled (dEC or dE2) is then divided by this coefficient when stop requests are sent.
Value 0 corresponds to a minimum ramp time.
Parameter that can be modified during operation or when stopped.