46
[1.3 SETTINGS]
(SEt-)
The adjustment parameters can be modified with the drive running or stopped.
(1) Range 0.01 to 99.99 s or 0.1 to 999.9 s or 1 to 9,000 s according to
[Ramp increment]
(Inr).
Code
Name/Description
Adjustment range
Factory setting
Inr
• [Ramp increment]
0.01 - 0.1 - 1
0.1
0.01
0.1
1
-
[0.01]
: Ramp up to 99.99 seconds
-
[0.1]
: Ramp up to 999.9 seconds
-
[1]
: Ramp up to 9,000 seconds
This parameter is valid for
[Acceleration]
(ACC)
,
[Deceleration]
(dEC)
,
[Acceleration 2]
(AC2)
and
[Deceleration 2]
(dE2)
.
ACC
• [Acceleration]
0.01 to 9,000 s (1)
3.0 s
Time to accelerate from 0 to the
[Rated motor freq.]
(FrS)
(page
61
). Make sure that this value is compatible
with the inertia being driven.
dEC
• [Deceleration]
0.01 to 9,000 s (1)
3.0 s
Time to decelerate from the
[Rated motor freq.]
(FrS)
(page
61
) to 0. Make sure that this value is compatible
with the inertia being driven.
AC2
• [Acceleration 2]
0.01 to 9,000 s (1)
5.0 s
*
See page
124
Time to accelerate from 0 to the
[Rated motor freq.]
(FrS)
. Make sure that this value is compatible with the
inertia being driven.
dE2
• [Deceleration 2]
0.01 to 9,000 s (1)
5.0 s
*
See page
124
Time to decelerate from the
[Rated motor freq.]
(FrS)
to 0. Make sure that this value is compatible with the
inertia being driven.
tA1
• [Begin Acc round]
0 to 100%
10%
*
See page
123
Rounding of start of acceleration ramp as a % of the
[Acceleration]
(ACC)
or
[Acceleration 2]
(AC2)
ramp time.
tA2
• [End Acc round]
10%
*
See page
123
- Rounding of end of acceleration ramp as a % of the
[Acceleration]
(ACC)
or
[Acceleration 2]
(AC2)
ramp
time.
- Can be set between 0 and (100% –
[Begin Acc round]
(tA1)
)
tA3
• [Begin Dec round]
0 to 100%
10%
*
See page
123
Rounding of start of deceleration ramp as a % of the
[Deceleration]
(dEC)
or
[Deceleration 2]
(dE2)
ramp time.
*
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and adjusted from within the configuration menu for the corresponding function, their description is detailed
in these menus, on the pages indicated, to aid programming.
DANGER
UNINTENDED EQUIPMENT OPERATION
• Check that changes made to the settings during operation do not present any danger.
• We recommend stopping the drive before making any changes.