77
[1.5 INPUTS / OUTPUTS CFG]
(I-O-)
The parameters in the
[1.5 INPUTS / OUTPUTS CFG]
(I-O-)
menu can only be modified when the drive is stopped and no run command
is present.
Code
Name/Description
Adjustment range
Factory setting
tCC
• [2/3 wire control]
[2 wire]
(2C)
2C
3C
-
[2 wire]
(2C)
-
[3 wire]
(3C)
2-wire control: This is the input state (0 or 1) or edge (0 to 1 or 1 to 0), which controls running or stopping.
Example of “source” wiring:
LI1: forward
LIx: reverse
3-wire control (pulse control): A “forward” or “reverse” pulse is sufficient to command starting, a “stop” pulse is
sufficient to command stopping.
Example of “source” wiring:
LI1: stop
LI2: forward
LIx: reverse
tCt
• [2 wire type]
[Transition]
(trn)
LEL
trn
PFO
-
[Level]
(LEL)
: State 0 or 1 is taken into account for run (1) or stop (0).
-
[Transition]
(trn)
: A change of state (transition or edge) is necessary to initiate operation, in order to prevent
accidental restarts after a break in the power supply.
-
[Fwd priority]
(PFO)
: State 0 or 1 is taken into account for run or stop, but the “forward” input always takes
priority over the “reverse” input.
rrS
• [Reverse assign.]
[No]
(nO)
+24
LI1
LIx
ATV 71
E
R 4 0
+24
LI1
LI2 LIx
ATV 71
E R 4 0
WARNING
UNINTENDED EQUIPMENT OPERATION
To change the assignment of
[2/3 wire control]
(tCC)
press the “ENT” key for 2 s.
It causes the following functions to return to factory setting:
[2 wire type]
(tCt)
and
[Reverse assign.]
(rrS)
below, and all functions which assign logic inputs and analog inputs.
The macro configuration selected will also be reset if it has been customized (loss of custom settings).
It is advisable to configure this parameter before configuring the
[1.6 COMMAND]
(CtL-)
and
[1.7 APPLICATION FUNCT.]
(FUn-)
menus.
Check that this change is compatible with the wiring diagram used.
Failure to follow these instructions can result in death or serious injury.