93
[1.5 INPUTS / OUTPUTS CFG]
(I-O-)
Code
Name/Description
Adjustment range
Factory setting
•
[R1 CONFIGURATION]
(continued)
r1d
• [R1 Delay time]
0 to 9,999 ms
0
The change in state only takes effect once the configured time has elapsed, when the information
becomes true.
The delay cannot be set for the
[No drive flt]
(FLt)
assignment, and remains at 0.
r1S
POS
nEG
• [R1 Active at]
[1]
(POS)
Configuration of the operating logic:
-
[1]
: State 1 when the information is true
-
[0]
: State 0 when the information is true
Configuration
[1]
(POS)
cannot be modified for the
[No drive flt]
(FLt),
assignment.
r1H
• [R1 Holding time]
0 to 9,999 ms
0
The change in state only takes effect once the configured time has elapsed, when the information
becomes false.
The holding time cannot be set for the
[No drive flt]
(FLt)
assignment, and remains at 0.
r2-
•
[R2 CONFIGURATION]
r2
• [R2 Assignment]
[Drv running]
(rUn)
LLC
OCC
dCO
Identical to R1 (see page
91
) with the addition of (shown for information only as these selections can only
be configured in the
[APPLICATION FUNCT.]
(Fun-)
) menu:
-
[Input cont.]
(LLC)
: Line contactor control
-
[Output cont]
(OCC)
: Output contactor control
-
[DC charging]
(dCO)
: DC bus precharging contactor control
r2d
• [R2 Delay time]
0 to 9,999 ms
0
The delay cannot be set for the
[No drive flt]
(FLt)
,
[Output cont]
(OCC)
,
[DC charging]
(dCO)
,
and
[Input cont.]
(LLC)
assignments, and remains at 0.
The change in state only takes effect once the configured time has elapsed, when the information
becomes true.
r2S
POS
nEG
• [R2 Active at]
[1]
(POS)
Configuration of the operating logic:
-
[1]
: State 1 when the information is true
-
[0]
: State 0 when the information is true
The
[1]
(POS)
configuration cannot be modified for the
[No drive flt]
(FLt)
,
[DC charging]
(dCO)
and
[Input cont.]
(LLC),
assignments.
r2H
• [R2 Holding time]
0 to 9,999 ms
0
The holding time cannot be set for the
[No drive flt]
(FLt)
,
[DC charging]
(dCO)
and
[Input cont.]
(LLC)
assignments, and remains at 0.
The change in state only takes effect once the configured time has elapsed, when the information
becomes false.