[1.8 FAULT MANAGEMENT]
(FLt-)
Parameter can be accessed in
[Expert]
mode.
Code
Name/Description
Adjustment range
Factory setting
InH-
•
[FAULT INHIBITION]
InH
• [Fault inhibit assign.]
[No]
(nO)
nO
LI1
-
-
-
To assign fault inhibit, press the “ENT” key for 2 s.
-
[No]
(nO)
: Function inactive, thereby preventing access to other function parameters.
-
[LI1]
(LI1)
:
:
-
[...]
(...)
: See the assignment conditions on page
109
.
If the assigned input or bit is at 0, fault monitoring is active. If the assigned input or bit is at 1, fault monitoring
is inactive. Active faults are reset on a rising edge (change from 0 to 1) of the assigned input or bit.
Note: The “Power Removal” function and any faults that prevent any form of operation are not affected by
this function.
A list of faults affected by this function appears on pages
220
to
224
.
InHS
nO
Frd
rrS
• [Forced Run]
[No]
(nO)
This parameter causes the run command to be forced in a specific direction when the input or bit for
fault inhibition is at 1, with priority over all other commands with the exception of “Power Removal”.
To assign forced run, press and hold down the “ENT” key for 2 s.
-
[No]
(nO)
: Function inactive
-
[Fw.For.Run]
(Frd)
: Forced forward run.
-
[Rev.For.Run]
(rrS)
: Forced
reverse run.
InHr
• [Forced Run Ref.]
0 to 500 or 1,000 Hz
according to rating
50 Hz
The parameter can be accessed if
[Forced Run]
(InHS)
is not
[No]
(nO)
This parameter causes the reference to be forced to the configured value when the input or bit for
fault inhibition is at 1, with priority over all other references. Value 0 = function inactive.
The factory setting changes to 60 Hz if
[Standard mot. freq]
(bFr)
=
[60 Hz NEMA]
(60)
.
CAUTION
Inhibiting faults results in the drive not being protected. This invalidates the warranty.
Check that the possible consequences do not present any risk.
Failure to follow these instructions can result in equipment damage.
DANGER
UNINTENDED EQUIPMENT OPERATION
• Check that it is safe to force the run command.
Failure to follow these instructions will result in death or serious injury.