95
[1.5 INPUTS / OUTPUTS CFG]
(I-O-)
Code
Name/Description
Adjustment range
Factory setting
LO1-
•
[LO1 CONFIGURATION]
Can be accessed if an ER40 option card "Logical extension" has been inserted
LO1
• [LO1 assignment]
[No]
(nO)
LLC
OCC
dCO
Identical to R1 (see page
91
) with the addition of (shown for information only as these selections can only
be configured in the
[APPLICATION FUNCT.]
(Fun-)
) menu:
-
[Input cont.]
(LLC)
: Line contactor control
-
[Output cont]
(OCC)
: Output contactor control
-
[[DC charging]
(dCO)
: DC bus precharging contactor control
LO1d
• [LO1 delay time]
0 to 9,999 ms
0
The delay cannot be set for the
[No drive flt]
(FLt)
,
[Output cont]
(OCC)
,
[DC charging]
(dCO)
,
and
[Input cont.]
(LLC)
assignments, and remains at 0.
The change in state only takes effect once the configured time has elapsed, when the information
becomes true.
LO1S
POS
nEG
• [LO1 active at]
[1]
(POS)
Configuration of the operating logic:
-
[1]
: State 1 when the information is true
-
[0]
: State 0 when the information is true
The
[1]
(POS)
configuration cannot be modified for the
[No drive flt]
(FLt)
,
[DC charging]
(dCO)
and
[Input cont.]
(LLC),
assignments.
LO1H
• [LO1 holding time]
0 to 9,999 ms
0
The holding time cannot be set for the
[No drive flt]
(FLt)
,
[DC charging]
(dCO)
and
[Input cont.]
(LLC)
assignments, and remains at 0.
The change in state only takes effect once the configured time has elapsed, when the information
becomes false.
LO2-
•
[LO2 CONFIGURATION]
Can be accessed if a ER40 option card "Logical extension" has been inserted
LO2
• [LO2 assignment]
[No]
(nO)
Identical to LO1.
LO2d
• [LO2 delay time]
0 to 9,999 ms
0
The delay cannot be set for the
[No drive flt]
(FLt)
,
[Output cont]
(OCC)
,
[DC charging]
(dCO)
,
and
[Input cont.]
(LLC)
assignments, and remains at 0.
The change in state only takes effect once the configured time has elapsed, when the information
becomes true.
LO2S
POS
nEG
• [LO2 active at]
[1]
(POS)
Configuration of the operating logic:
-
[1]
: State 1 when the information is true
-
[0]
: State 0 when the information is true
The
[1]
(POS)
configuration cannot be modified for the
[No drive flt]
(FLt)
,
[DC charging]
(dCO)
and
[Input cont.]
(LLC),
assignments.
LO2H
• [LO2 holding time]
0 to 9,999 ms
0
The holding time cannot be set for the
[No drive flt]
(FLt)
,
[DC charging]
(dCO)
and
[Input cont.]
(LLC)
assignments, and remains at 0.
The change in state only takes effect once the configured time has elapsed, when the information
becomes false.