H10: Skip Frequency Select
Range:
0 - 1 (Default: 0)
Description:
This parameter activates the skip frequencies (see H11-H16).
H11-H16: Frequency Jump
Range:
0.1-400Hz
Description:
To prevent undesirable resonance and vibration on the structure of a
machine, this function locks out the resonance frequencies from operation.
Three different jump frequency ranges can be set. This jumping of
frequencies does not occur while accelerating or decelerating. It only occurs
during continuous operation.
Run frequency cannot be set within the range of H11 thru H16. The
frequency values of the low numbered parameters cannot be set above those
of the high numbered ones. Settable within the range of F21 and F23.
z
Note
: When the reference frequency is set inside the jump frequency, the
output frequency goes to the frequency marked by “_” symbol.
z
Note
: If one frequency jump range is required, set all ranges to the same
one range.
H17: S-Curve Accel/Decel Start Side
Range:
1-100% (40%)
Description:
When F2 is set to S-curve, this parameter shapes the beginning of the
S-curve for smooth acceleration and deceleration.
H18: S-Curve Accel/Decel End Side
Range:
1-100% (40%)
Description:
When F2 is set to S-curve, this parameter shapes the end of the S-curve for
smooth acceleration and deceleration.
85
6 - Parameter Descriptions
Содержание RSi GX Series
Страница 7: ...1 Introduction 1...
Страница 15: ...2 Technical Specifications 9...
Страница 24: ...Notes 18 2 TECHNICAL SPECIFICATIONS...
Страница 25: ...3 Receiving and Installation 19...
Страница 41: ...4 Operation 35...
Страница 53: ...5 Parameter List 47...
Страница 62: ...Notes 56 5 Parameter List...
Страница 63: ...6 Parameter Descriptions 57...
Страница 135: ...7 Remote Communication 129...
Страница 149: ...8 Troubleshooting Maintenance 143...
Страница 162: ...Notes 156 8 Troubleshooting Maintenance...
Страница 163: ...9 Options 157...
Страница 165: ...10 Appendices 159...