I6 - I10: Bias and Gain of the -10 to 0V Signal
Range:
Description:
These parameters are used to adjust the scaling of the V1 (-10 to 0V) analog
input signal. The scaling and slope of the analog signal is adjusted by setting
parameters I2-I5. A filter time can also be set to reduce the affects of noise
on the analog signal. This parameter is active if Frq is set to 3 or 5.
I6 is the filtering time constant for the V1 (0-10Vdc) input. Increasing this
value will reduce the drive's response to noise. However, increasing this
parameter will also make the drive respond slower to speed changes.
112
6 - Parameter Descriptions
Set freq.
I8
10Hz
50Hz
8V
V0 input
2V
I7
I9
I10
Code
Default
Setting
Code
Default
Setting
I7
0V
0-10V
I9
10V
0~10V
I8
0Hz
0~Max.
freq
I10
60Hz
0~Max.
freq