50
5 - Parameter List
Code
[FU1]
Parameter Name
Setting Range
Factory
Default
Adj. during
run
Page
F31
4
User V/F Frequency 1
0-400 [Hz]
15.00 [Hz]
No
76
F32
User V/F Voltage 1
0-100 [%]
25 [%]
No
F33
User V/F Frequency 2
0-400 [Hz]
30.00 [Hz]
No
F34
User V/F Voltage 2
0-100 [%]
50 [%]
No
F35
User V/F Frequency 3
0-400 [Hz]
45.00 [Hz]
No
F36
User V/F Voltage 3
0-100 [%]
75 [%]
No
F37
User V/F Frequency 4
0-400 [Hz]
60.00 [Hz]
No
F38
User V/F Voltage 4
0-100 [%]
100 [%]
No
F39
Output Voltage Adjustment
40-110 [%]
100 [%]
No
77
F40
Energy Save Level
0-30 [%]
0 [%]
Yes
78
F50
Electronic Thermal Selection
0 (No)
1 (Yes)
0 (No)
Yes
78
F51
1
Electronic Thermal Level for 1
minute
50-200 [%]
150 [%]
Yes
79
F52
Electronic Thermal Level for
continuous
100 [%]
Yes
79
F53
Electronic Thermal
Characteristic selection (Motor
Type)
0 (Self-cool)
1 (Forced-cool)
0
Self-cool
Yes
80
F54
Overload Warning Level
30-150 [%]
150 [%]
Yes
80
F55
Overload Warning Hold Time
0-30 [sec]
10 [sec]
Yes
81
F56
Overload Trip Select
0 (No)
1 (Yes)
1 (Yes)
Yes
81
F57
Overload Trip Level
30-200 [%]
180 [%]
Yes
81
F58
Overload Trip Time
0-60 [sec]
60 [sec]
Yes
82
F59
Stall Prevention Mode Select
000-111 (bit set)
Bit 0: during Accel.
Bit 1: during steady
speed
Bit 2: during decel
000
No
82
F60
Stall Prevention Level
30-150 [%]
150 [%]
No
83
Содержание RSi GX Series
Страница 7: ...1 Introduction 1...
Страница 15: ...2 Technical Specifications 9...
Страница 24: ...Notes 18 2 TECHNICAL SPECIFICATIONS...
Страница 25: ...3 Receiving and Installation 19...
Страница 41: ...4 Operation 35...
Страница 53: ...5 Parameter List 47...
Страница 62: ...Notes 56 5 Parameter List...
Страница 63: ...6 Parameter Descriptions 57...
Страница 135: ...7 Remote Communication 129...
Страница 149: ...8 Troubleshooting Maintenance 143...
Страница 162: ...Notes 156 8 Troubleshooting Maintenance...
Страница 163: ...9 Options 157...
Страница 165: ...10 Appendices 159...