H19: Input/Output Phase Loss Protection
Range:
0-3 (Default: 0 Disabled)
Description:
This function is used to fault the drive output in case of input/output phase
loss of power input or drive output.
Display:
Function:
0
Disabled
1
Output Phase protection
2
Input Phase protection
3
Input/Output Phase Protection
Output Phase Loss Protection
•
Set H19 value to 1.
•
Output phase loss: The drive faults if there is a phase loss on the U,V and
W terminals.
•
Input phase loss: The drive faults if there is a phase loss in the R, S and T
input terminals.
Related Functions: H22-H25 [Speed Search]
86
6 - Parameter Descriptions
Setting Range
H19
Description
2nd Bit
1st bit
0
0
00
Phase loss protection does not work.
0
1
01
Protect drive from output phase loss.
1
0
10
Protect drive from input phase loss.
1
1
11
Protect drive from input and output phase loss.
Set H33 [Motor rated current] correctly. If the actual
motor rated current and the value of H33 are different,
output phase loss protection function may not function.
CAUTION
Содержание RSi GX Series
Страница 7: ...1 Introduction 1...
Страница 15: ...2 Technical Specifications 9...
Страница 24: ...Notes 18 2 TECHNICAL SPECIFICATIONS...
Страница 25: ...3 Receiving and Installation 19...
Страница 41: ...4 Operation 35...
Страница 53: ...5 Parameter List 47...
Страница 62: ...Notes 56 5 Parameter List...
Страница 63: ...6 Parameter Descriptions 57...
Страница 135: ...7 Remote Communication 129...
Страница 149: ...8 Troubleshooting Maintenance 143...
Страница 162: ...Notes 156 8 Troubleshooting Maintenance...
Страница 163: ...9 Options 157...
Страница 165: ...10 Appendices 159...