Altitude Derating
2.4
Altitude Derating
Benshaw VFDs are capable of operating at altitudes up to 3,300 feet (1000 meters) without
requiring an altitude derate. Table 3 provides the derating percentage to be considered
when using a drive above 3,300 feet (1000 meters).
z
Note:
For derating above 10,000ft consult Benshaw.
Thermal Derating
2.5
Thermal Derating
The ambient operating temperature range of the RSi GX is as follows:
•
NEMA 1 0-40°C
13
2 - TECHNICAL SPECIFICATIONS
Altitude
Percent Derating (Amps)
3,300 feet
1,006 meters
0.0%
4,300 feet
1,311 meters
3.0%
5,300 feet
1,615 meters
6.0%
6,300 feet
1,920 meters
9.0%
7,300 feet
2,225 meters
12.0%
8,300 feet
2,530 meters
15.0%
9,300 feet
2,835 meters
18.0%
Table 3: Altitude Derating