F4: Stop Mode Select
Range:
0 - 2 (Default: 0)
Description:
This parameter sets the stopping method for the drive.
Display:
Function:
0
Decelerate to stop
1
DC brake to stop
2
Free run to stop
Decel: The drive stops using the deceleration pattern. Select 0 in F30.
DC-brake: The drive stops with DC injection braking. The drive will output
a DC voltage when the frequency goes below the DC injection braking
frequency during deceleration (see F8-F11, page 68-69).
Free-run (Coast to stop): The drive stops outputting voltage immediately
when the stop signal is commanded.
67
6 - Parameter Descriptions
Output Frequency
Time
FX -CM
ON
Output Voltage
Time
Time
Stop Command
[Stop Mode: 'Decel']
Output Frequency
Time
FX -CM
ON
Output Voltage
Time
Time
Stop Command
[DCBr Freq]
[DCBr Value]
t1
t2
t1: FUN -24
t2: FU N-26
[Stop Mode: 'DC-brake']
Output Frequency
Time
FX
-
CM
ON
Output Voltage
Time
Time
Stop Command
Output cutoff
Output cutoff
[Stop Mode: 'Free-run']
Содержание RSi GX Series
Страница 7: ...1 Introduction 1...
Страница 15: ...2 Technical Specifications 9...
Страница 24: ...Notes 18 2 TECHNICAL SPECIFICATIONS...
Страница 25: ...3 Receiving and Installation 19...
Страница 41: ...4 Operation 35...
Страница 53: ...5 Parameter List 47...
Страница 62: ...Notes 56 5 Parameter List...
Страница 63: ...6 Parameter Descriptions 57...
Страница 135: ...7 Remote Communication 129...
Страница 149: ...8 Troubleshooting Maintenance 143...
Страница 162: ...Notes 156 8 Troubleshooting Maintenance...
Страница 163: ...9 Options 157...
Страница 165: ...10 Appendices 159...