62
6 - Parameter Descriptions
CUr: Output Current
Range:
Description:
Displays the output current to the motor.
•
Drive output current can be monitored in CUr.
rPM: Motor RPM
Range:
Description:
This code displays the output current of the drive in RPM while the motor is
running.
Use the following equation to scale the mechanical speed using H74 [Gain
for Motor Speed display] if you want to change the motor speed display to
rotation speed (r/min) or mechanical speed (m/min).
Motor speed = 120* (F/P) * FU2-74
Where, F: output frequency and P: the number of motor pole
dCL: Inverter DC Link Voltage
Range:
Description:
Displays DC link voltage inside the drive.
•
Inverter DC link voltage can be monitored in dCL.
•
2 times the value of input voltage is displayed while motor is stopped.
vOL: User Display Select
Range:
vOL, POr, tOr (Default: vOL)
Description:
This parameter displays the value of the parameter selected in H73
(Monitoring item select).
Содержание RSi GX Series
Страница 7: ...1 Introduction 1...
Страница 15: ...2 Technical Specifications 9...
Страница 24: ...Notes 18 2 TECHNICAL SPECIFICATIONS...
Страница 25: ...3 Receiving and Installation 19...
Страница 41: ...4 Operation 35...
Страница 53: ...5 Parameter List 47...
Страница 62: ...Notes 56 5 Parameter List...
Страница 63: ...6 Parameter Descriptions 57...
Страница 135: ...7 Remote Communication 129...
Страница 149: ...8 Troubleshooting Maintenance 143...
Страница 162: ...Notes 156 8 Troubleshooting Maintenance...
Страница 163: ...9 Options 157...
Страница 165: ...10 Appendices 159...