F60: Stall Prevention Level
Range:
30-150% (Default: 150%)
Description:
This parameter sets the amount of current to activate stall prevention
function during Accel, Constant or Decel run.
The set value is the percentage of the H33 [Motor rated current].
F60 is used to prevent the motor from stalling by reducing the drive output
frequency until the motor current decreases below the stall prevention level.
This function can be selected for each mode of acceleration, steady speed
and deceleration via bit combination.
•
During acceleration: Motor starts deceleration when current exceeding the
value set in F60 flows.
•
During constant run: Motor decelerates when current exceeding the value
set in F60 flows.
•
During deceleration: Motor deceleration is stopped when drive DC link
voltage rises above a certain voltage level.
•
F60: The value is set as the percent of motor rated current (H33).
z
Note:
The set value is the percentage of H33 [Rated Motor Current].
6.3
Function Group 2
H0: Jump Code]
Range:
0-95 (Default:1)
Description:
This parameter allows the user to "jump" to any parameter without scrolling
through the group. Enter the desired parameter number, and the drive will
"jump" to that parameter.
83
6 - Parameter Descriptions
Содержание RSi GX Series
Страница 7: ...1 Introduction 1...
Страница 15: ...2 Technical Specifications 9...
Страница 24: ...Notes 18 2 TECHNICAL SPECIFICATIONS...
Страница 25: ...3 Receiving and Installation 19...
Страница 41: ...4 Operation 35...
Страница 53: ...5 Parameter List 47...
Страница 62: ...Notes 56 5 Parameter List...
Страница 63: ...6 Parameter Descriptions 57...
Страница 135: ...7 Remote Communication 129...
Страница 149: ...8 Troubleshooting Maintenance 143...
Страница 162: ...Notes 156 8 Troubleshooting Maintenance...
Страница 163: ...9 Options 157...
Страница 165: ...10 Appendices 159...