6.4
I/O Group
I0: Jump Code
Range:
0 - 64 (Default: 1)
Description:
This parameter allows the user to "jump" to any parameter without scrolling
through the group. Enter the desired parameter number, and the drive will
"jump" to that parameter.
I1 - I5: Bias and Gain of the -10 to 0V Signal
Range:
0 - 9999 (10)
Description:
These parameters are used to adjust the scaling of the V1 (-10 to 0V) analog
input signal. The scaling and slope of the analog signal is adjusted by setting
parameters I2-I5. A filter time can also be set to reduce the affects of noise
on the analog signal. This parameter is active if Frq is set to 5 or 6.
I1 is the filtering time constant for the V1 (0-10Vdc) input. Increasing this
value will reduce the drive's response to noise. However, increasing this
parameter will also make the drive respond slower to speed changes.
111
6 - Parameter Descriptions
-8V
50Hz
Set freq.
-2V
10Hz
I2
I3
I5
V1 input
I4
Code
Default
Setting
Code
Default
Setting
I2
0V
-10~0
I4
-10V
0~-10V
I3
0Hz
0~Max.
freq
I5
60Hz
0~Max.
freq
Содержание RSi GX Series
Страница 7: ...1 Introduction 1...
Страница 15: ...2 Technical Specifications 9...
Страница 24: ...Notes 18 2 TECHNICAL SPECIFICATIONS...
Страница 25: ...3 Receiving and Installation 19...
Страница 41: ...4 Operation 35...
Страница 53: ...5 Parameter List 47...
Страница 62: ...Notes 56 5 Parameter List...
Страница 63: ...6 Parameter Descriptions 57...
Страница 135: ...7 Remote Communication 129...
Страница 149: ...8 Troubleshooting Maintenance 143...
Страница 162: ...Notes 156 8 Troubleshooting Maintenance...
Страница 163: ...9 Options 157...
Страница 165: ...10 Appendices 159...