drv: Drive Mode (run/stop method)
Range:
0 - 3 (Default: 1)
Description:
This parameter sets the method for starting and stopping the drive.
Display:
Function:
0
Run/Stop via Run/Stop key on the keypad
1
P1 (FX): Motor forward run, P2 (RX): Motor reverse run
2
P1 (FX): Run/Stop enable, P2 (RX): Reverse rotation
select
3
RS485 communication
59
6 - Parameter Descriptions
Output frequency
FX-CM
Time
Run/Stop
Direction
ON
RX-CM
ON
Forward
Reverse
[Drive Mode: 'Fx/Rx-1']
Output frequency
FX-CM
Time
Forward run
Reverse run
ON
RX-CM
ON
Forward
Reverse
[Drive Mode: 'Fx/Rx-2']