3.9
Recommended AC Reactors
3.9.1
Keypad
Wiring the Keypad
Keypad is installed before shipping for standard type models as shown below. When using
an optional remote cable, install the buffer cover and connect the remote cable. If the
keypad is not connected properly, the letters will not be displayed.
z
Note
: Do not connect the keypad and remote cable while the drive power is introduced.
z
Note:
Do not touch the live part of the keypad connector. Doing this may cause personal
injury or electric shock.
33
3 - RECEIVING AND INSTALLATION
Keypad
(Detachable)
Model
External Fuse
AC Reactor
Current[A]
Voltage[V]
RSi001GX2B
10A
500
2.13mH, 5.7A
RSi002GX2B
15A
500
1.20mH, 10A
RSi003GX2B
25A
500
0.88mH, 14A
RSi005GX2B
40A
500
0.56mH, 20A
RSi001GX4B
10A
500
8.63mH, 1.3A
RSi002GX4B
10A
500
4.81mH, 4.8A
RSi003GX4B
20A
500
3.23mH, 7.5A
RSi005GX4B
20A
500
2.34mH, 10A
•
Short Circuit Rating
"Suitable For Use ON a Circuit Capable of Delivering Not More Than 5,000RMS Symmetrical
Amperes. 240V drives or 480V drives Volts Maximum."
•
Short Circuit FUSE/BREAKER Marking
Use Class H or K5 UL Kisted Input Fuse and UL Listed Breaker Only. See the table above for the
voltage and current rating of the fuse and the breaker.
Содержание RSi GX Series
Страница 7: ...1 Introduction 1...
Страница 15: ...2 Technical Specifications 9...
Страница 24: ...Notes 18 2 TECHNICAL SPECIFICATIONS...
Страница 25: ...3 Receiving and Installation 19...
Страница 41: ...4 Operation 35...
Страница 53: ...5 Parameter List 47...
Страница 62: ...Notes 56 5 Parameter List...
Страница 63: ...6 Parameter Descriptions 57...
Страница 135: ...7 Remote Communication 129...
Страница 149: ...8 Troubleshooting Maintenance 143...
Страница 162: ...Notes 156 8 Troubleshooting Maintenance...
Страница 163: ...9 Options 157...
Страница 165: ...10 Appendices 159...