F58: Overload Trip Time
Range:
0-60 sec. (Default: 60sec.)
Description:
This parameter turns off the drive output when the F57 [Overload trip level]
of current flows to the motor for F58 [Overload trip time].
F59: Stall Prevention Mode Select
Range:
000-111 (bit set) (Default: 000)
Description:
This parameter stops accelerating during acceleration, decelerating during
constant speed run and stops decelerating during deceleration, to prevent the
drive from faulting.
F59 follows the conventions used in I25 (Input Terminal Status Display)
and I26 (Input Terminal Status Display, page 115) to show the ON (bit set)
status with the 7-segment keypad throughout this manual.
•
Stall Prevention (F9) can be set as the table below:
•
For example, set F59 to 3 to make stall prevention active during
Acceleration and constant run.
•
When stall prevention is executed during acceleration or deceleration,
Accel/Decel time may take longer than the user-setting time.
•
When stall prevention is activated during constant run, t1, t2 executed in
accordance with the value set in ACC - [Accel time] and dEC - [Decel
time], (see F60).
82
6 - Parameter Descriptions
F29
Stall
Prevention
Setting
During
Deceleration
During
Constant
Speed
During
Acceleration
Bit 2
Bit 1
Bit 0
0
-
-
-
1
-
-
ü
2
-
ü
-
3
-
ü
ü
4
ü
-
-
5
ü
-
ü
6
ü
ü
-
7
ü
ü
ü
Содержание RSi GX Series
Страница 7: ...1 Introduction 1...
Страница 15: ...2 Technical Specifications 9...
Страница 24: ...Notes 18 2 TECHNICAL SPECIFICATIONS...
Страница 25: ...3 Receiving and Installation 19...
Страница 41: ...4 Operation 35...
Страница 53: ...5 Parameter List 47...
Страница 62: ...Notes 56 5 Parameter List...
Страница 63: ...6 Parameter Descriptions 57...
Страница 135: ...7 Remote Communication 129...
Страница 149: ...8 Troubleshooting Maintenance 143...
Страница 162: ...Notes 156 8 Troubleshooting Maintenance...
Страница 163: ...9 Options 157...
Страница 165: ...10 Appendices 159...