H20: Power ON Start Select
Range:
0-1 (Default: 0)
Description:
This parameter is activated when DRV is set to 1 or 2 (Run/Stop via Control
terminal).
Display:
Function:
0
The drive requires the start command to open and reclose
upon power loss.
1
The drive will restart upon return of power if run
command is still active.
H21: Restart After Fault Reset Selection
Range:
0 - 1 (Default:0)
Description:
This parameter is activated when DRV is set to 1 or 2 (Run/Stop via Control
terminal).
Display:
Function:
0
The drive requires the start command to open and reclose
upon a fault reset.
1
The drive will restart upon a fault reset if run command is
still active.
87
6 - Parameter Descriptions
Particular attention must be directed to this function due
to potential hazard as motor starts to run suddenly upon
applying AC input power.
CAUTION
Particular attention must be directed to this function due to
potential hazard as motor starts to run suddenly upon applying
AC input power.
CAUTION
Run
command
Frequency
Input voltage
When H20 is 0
When H20 is 1
Содержание RSi GX Series
Страница 7: ...1 Introduction 1...
Страница 15: ...2 Technical Specifications 9...
Страница 24: ...Notes 18 2 TECHNICAL SPECIFICATIONS...
Страница 25: ...3 Receiving and Installation 19...
Страница 41: ...4 Operation 35...
Страница 53: ...5 Parameter List 47...
Страница 62: ...Notes 56 5 Parameter List...
Страница 63: ...6 Parameter Descriptions 57...
Страница 135: ...7 Remote Communication 129...
Страница 149: ...8 Troubleshooting Maintenance 143...
Страница 162: ...Notes 156 8 Troubleshooting Maintenance...
Страница 163: ...9 Options 157...
Страница 165: ...10 Appendices 159...