Display:
Function:
0
Keypad setting 1 (Digital).
1
Keypad setting 2 (Digital).
2
V1 1: -10 to +10V (Analog)
3
V1 2: 0 to +10V (Analog)
4
Terminal I: 0 to 20mA (Analog)
5
Terminal VI setting 1 + Terminal I (Analog)
6
Terminal V1 setting 2+ Terminal I (Analog)
See I17 - I24, and drv2.
6.2
Function Group 1
F0: Jump Code
Range:
0 - 60 (Default: 1)
Description:
This parameter allows the user to "jump" to any parameter without scrolling
through the group. Enter the desired parameter number, and the drive will
"jump" to that parameter.
F1: Forward/Reverse Run Disable
Range:
0 - 2 (Default: 0)
Description:
This function allows the user to lockout forward or reverse operation of the
motor. This function may be used for loads that rotate only in one direction
such as fans and pumps.
Display:
Function:
0
Forward and reverse run enable
1
Forward run disable
2
Reverse run disable
65
6 - Parameter Descriptions
Содержание RSi GX Series
Страница 7: ...1 Introduction 1...
Страница 15: ...2 Technical Specifications 9...
Страница 24: ...Notes 18 2 TECHNICAL SPECIFICATIONS...
Страница 25: ...3 Receiving and Installation 19...
Страница 41: ...4 Operation 35...
Страница 53: ...5 Parameter List 47...
Страница 62: ...Notes 56 5 Parameter List...
Страница 63: ...6 Parameter Descriptions 57...
Страница 135: ...7 Remote Communication 129...
Страница 149: ...8 Troubleshooting Maintenance 143...
Страница 162: ...Notes 156 8 Troubleshooting Maintenance...
Страница 163: ...9 Options 157...
Страница 165: ...10 Appendices 159...