Please see H50 to H54 for more detail.
[SVC]:
Use sensorless vector control when 1) high starting torque is
required at low speeds 2) the load fluctuates 3) fast torque response times
are needed.
For proper operation, set H42-H46.
Set “Yes” in H41 [Auto tuning] first before using this control.
H41: Auto Tuning
Range:
0 - 1 (Default: 0)
Description:
All of the motor parameters can be tuned by setting “YES (1)”. Auto tuning
is deactivated when “No (0)” is selected.
The auto tuning function automatically measures the motor parameters
needed for the control selected in H40 [Control mode] such as stator
resistance, rotor resistance, leakage inductance, no-load current and Encoder
feedback frequency.
z
Note
: The rated current, voltage, efficiency and slip described in the
motor nameplate should be entered before performing auto tuning. The load
should not be connected when performing an auto tune in H41.. If efficiency
is not indicated on the nameplate, use the default value.
H42: Stator Resistance (Rs)
Range:
0 - 14
W
Description:
This is the value of the motor stator resistance.
96
6 - Parameter Descriptions
Содержание RSi GX Series
Страница 7: ...1 Introduction 1...
Страница 15: ...2 Technical Specifications 9...
Страница 24: ...Notes 18 2 TECHNICAL SPECIFICATIONS...
Страница 25: ...3 Receiving and Installation 19...
Страница 41: ...4 Operation 35...
Страница 53: ...5 Parameter List 47...
Страница 62: ...Notes 56 5 Parameter List...
Страница 63: ...6 Parameter Descriptions 57...
Страница 135: ...7 Remote Communication 129...
Страница 149: ...8 Troubleshooting Maintenance 143...
Страница 162: ...Notes 156 8 Troubleshooting Maintenance...
Страница 163: ...9 Options 157...
Страница 165: ...10 Appendices 159...