[IOL]
MO-MG is CLOSED when the output current is above the 150% of rated
drive current for 36 seconds. If this situation is continued for 1 minute, drive
will cut off its output and displays ‘IOL’ (Inverter overload) Trip. See the
nameplate for the rated drive current.
[Stall]
MO-MG is CLOSED when the drive is in the stall prevention mode.
Related Functions: F59 [Stall Prevention Mode], F60 [Stall Prevention
Level]
123
6 - Parameter Descriptions