3.6.4
Power and Motor Connection
31
3 - RECEIVING AND INSTALLATION
Drive Capacity
Terminal
Screw
Size
Screw
Torque
1)
Kgf
cm /
lb-in
Grounding
Method
Wire
2)
mm
2
AWG
R,S,T
U,V,W
R,S,T
U,V,W
2
0
0
V
1.0HP
M3
10/8.7
Type 3
2
2
14
14
2.0HP
M3
10/8.7
2
2
14
14
3.0HP
M3
15/13
2
2
14
14
5.0HP
M3
15/13
3.5
3.5
12
12
4
0
0
V
1.0HP
M3
10/8.7
Special
Type 3
2
2
14
14
2.0HP
M3
15/13
2
2
14
14
3.0HP
M3
15/13
2
2
14
14
5.0HP
M3
15/13
2
2
14
14
1) Apply the rated torque to terminal screws. Loose terminal screws can cause a short circuit or
other malfunction. Over tightening the terminal screws/bolts may permanently damage the
terminals.
Motor should be connected to the
U,V,W terminals.
If the forward swich (FX) is on, the
motor should rotate counter clockwise
when viewed rom the load side of the
motor. If the mtor rotates in the reverse
direction, switch the U and V terminals.
Power supply must be connected o
the R,ST terminals.
Connecting it to the U,V,W terminals
causes internal damages to the drive
Arrangng the phase sequence is not
necessary.
Motor
R
S
T
B1 B2
U
V
W
DB
Resistor
3 Power Input: R,S,T
1 Power Input: R,T
f
f
Содержание RSi GX Series
Страница 7: ...1 Introduction 1...
Страница 15: ...2 Technical Specifications 9...
Страница 24: ...Notes 18 2 TECHNICAL SPECIFICATIONS...
Страница 25: ...3 Receiving and Installation 19...
Страница 41: ...4 Operation 35...
Страница 53: ...5 Parameter List 47...
Страница 62: ...Notes 56 5 Parameter List...
Страница 63: ...6 Parameter Descriptions 57...
Страница 135: ...7 Remote Communication 129...
Страница 149: ...8 Troubleshooting Maintenance 143...
Страница 162: ...Notes 156 8 Troubleshooting Maintenance...
Страница 163: ...9 Options 157...
Страница 165: ...10 Appendices 159...