H91 & H92: Parameter Read/Write
Range:
0 - 1 (Default:0)
Description:
Used to read/write drive parameters when using an optional remote keypad.
This is useful when programming drives to have same parameter settings.
The keypad can read (upload) the parameter settings from one drive and can
write (download) them to other drives.
Parameter Read:
•
Move to parameter H91.
•
Press Enter (
) key once. Keypad display will be 0.
•
Press Up (
p
) key once. Keypad display will be 1.
•
Press Enter (
) key twice. Keypad display will be 1.
•
H91 is displayed when Parameter read is finished.
Parameter Write:
•
Move to parameter H92.
•
Press Enter (
) key once. Keypad display will be 0.
•
Press Up (
p
) key once. Keypad display will be 1.
•
Press Enter (
) key twice. Keypad display will be 1.
•
H92 is displayed when Parameter write is finished.
108
6 - Parameter Descriptions
Take caution when Parameter write (H92) is executed. By
doing this, parameters in drive are cleared and parameters
in remote keypad are copied to the drive.
CAUTION
Set H91 to “Yes” and
press Enter key to read
the parameters.
Install the keypad into the next
drive and set H92 to “Yes”. Then
press Enter to download the parameters.
Move remote LED
keypad to the second
drive.
Æ
Æ
V R
E FRE UEN
DR VE
RUN
ENT
RESET
STOP
SET
RUN
FWD
REV
V R
E FRE UEN
DR VE
RUN
ENT
RESET
STOP
SET
RUN
FWD
REV
Содержание RSi GX Series
Страница 7: ...1 Introduction 1...
Страница 15: ...2 Technical Specifications 9...
Страница 24: ...Notes 18 2 TECHNICAL SPECIFICATIONS...
Страница 25: ...3 Receiving and Installation 19...
Страница 41: ...4 Operation 35...
Страница 53: ...5 Parameter List 47...
Страница 62: ...Notes 56 5 Parameter List...
Страница 63: ...6 Parameter Descriptions 57...
Страница 135: ...7 Remote Communication 129...
Страница 149: ...8 Troubleshooting Maintenance 143...
Страница 162: ...Notes 156 8 Troubleshooting Maintenance...
Страница 163: ...9 Options 157...
Страница 165: ...10 Appendices 159...