H73: Monitoring Item Select
Range:
0 - 2 (Default: 0)
Description:
The selected item in H73 [Monitoring item select] can be monitored via
vOL - [User display select]. If output power or torque is selected, Por or tOr
will be displayed. Enter motor efficiency indicated on motor nameplate in
H36 to display correct torque.
Display:
Function:
0
Output voltage [V]
1
Output power [kW]
2
Torque [kgf
m]
H74: Gain for Motor RPM Display
Range:
1-1000% (Default: 100)
Description:
This parameter is used to change the motor speed display to rotating speed
(r/min) or mechanical speed (rpm).
Motor RPM can be monitored in rPM:
•
When H40 is set to 0 {V/F control} or 1 {PID control}, the drive output
frequency (f) is displayed in RPM using the formula below. Motor slip is
not considered.
RPM
f
H
H
=
´
æ
è
çç
ö
ø
÷÷´
120
31
74
100
•
H31: Enter the number of rated motor poles on the nameplate.
•
H74: This parameter is used to change the motor speed display to rotating
speed (r/min) or mechanical speed (m/min).
H75: DB Resistor Operating Rate Limit Select
Range:
0 - 1 (Default: 1)
Description:
This must be set when using an external DB resistor. The duty is calculated
by ‘%ED=Decel time * 100 / (Accel time + Steady speed time + Decel time
+ Stop status time)’.
Display:
Function:
0
No Limit
1
ED is limited as the setting in H76
103
6 - Parameter Descriptions
Содержание RSi GX Series
Страница 7: ...1 Introduction 1...
Страница 15: ...2 Technical Specifications 9...
Страница 24: ...Notes 18 2 TECHNICAL SPECIFICATIONS...
Страница 25: ...3 Receiving and Installation 19...
Страница 41: ...4 Operation 35...
Страница 53: ...5 Parameter List 47...
Страница 62: ...Notes 56 5 Parameter List...
Страница 63: ...6 Parameter Descriptions 57...
Страница 135: ...7 Remote Communication 129...
Страница 149: ...8 Troubleshooting Maintenance 143...
Страница 162: ...Notes 156 8 Troubleshooting Maintenance...
Страница 163: ...9 Options 157...
Страница 165: ...10 Appendices 159...