[Ovt]
MO-MG is CLOSED when high voltage is on the DC link.
[Lvt]
MO-MG is CLOSED when low voltage trip occurs due to DC link voltage
under 400V(200V).
[OH]
MO-MG is CLOSED when the heat sink of the drive is above the reference
level.
[Command Loss]
MO-MG is CLOSED when reference frequency is lost.
Related Functions: I11 [Criteria for Analog Signal Loss],
I48 [Oreating Method at Signal Loss],
I49 [Waiting Time for Time Out]
124
6 - Parameter Descriptions
[MG configured as ‘LV’]
MO-MG
ON
DC Link Voltage
Time
Time
LV Level (200V DC or 400V DC)
[MG configured as ‘OV’]
MO-MG
ON
DC Link Voltage
Time
Time
380V
(760V)
370V
(740V)
OV Level (380V DC or 760V DC)