18
3.3
Before Powering Up
Place the control panel in a dry and well-ventilated location, as far as possible from any heat
sources.
High power RF transmitters should be placed at least 2 meters away from the control panel.
Check for proper grounding. Uncharged your body by touching the Ground terminal.
Make sure polarity of detectors, keypads and other devices are correct.
Connect a momentary voltage to the siren; making sure a ‘beep’ is heard. If no beep, check for
short circuit or improperly connected wires.
Connect AC power to initial Power Up (transformer only). Connect battery only after keypad and
sensors seem to be operating properly. (Do not Power-up with battery alone.) Verify power
polarity of keypads.
Do not connect any devices to the battery terminals.
Series 860: Use only Fast Blow type fuse, size 20 x 5 mm, current 1.25A (supplied).
3.4
Connecting Smoke Detectors
The
EasyLoader
Series accommodate Ionization or Optical type 12V Smoke Detectors. Up to five
smoke detectors may be connected to each zone. Note: Most smokes output is Open Collector type;
program the Smoke zone as Fire and Normally Open zone type.
Panels are compatible with 12V smoke detectors with open collector or relay (-) output on alarm.
Smoke detector is reset by programming the SLO output to drive -V while holding-down key 9 (a
momentary switch or relay that disconnects power to smoke detector after a smoke alarm). Refer to
smoke wiring diagram.
When Fire Alarm occurs; hold-down key ‘9’ for reset, then enter valid code to disable alarm.
For connecting Smoke detector and EOL resistor, use a N.C. (normally close) smoke.
Reset Relay (or switch)
Relay or Switch mode, should be Normaly Close.
For reset cut power for Smoke during 3 Sec's
Connect EOL Resistor at last smoke
Av-Gad Systems
SLO
AV-2000 Panel
- +
+12V, Aux. Power
ZONE
-V
-V
AV-01 Relay Muodle
Aux. Power
1
2
4
3
+Vin
+Vout
-V
-R
Type NE_2000 (D Ver.)
1
2
4
3
+Vin
+Vout
-V
-R
Type NE_2000 (D Ver.)
-V switched by the Rest relay
Drive -V at Reset
To zone
N.C. Mode
Figure 4: Smoke Detectors (NE-2000) Wiring