Three-phase active
energy measurement
("EP meas 3ph")
0:
Disabled
1:
Enabled
-
0: Disabled
Enables/disables the active energy measurement.
Three-phase reactive
energy measurement
("EQ meas 3ph")
0:
Disabled
1:
Enabled
-
0: Disabled
Enables/disables the reactive energy measurement.
Three-phase energy
pre x
("E 3ph M or k")
0: Mega
1: Kilo
-
0: Mega
De nes whether energy is measured with the pre x 'kilo' (10
3
)
or 'mega' (10
6
).
PQ Quadrant
0:
Unde ned
1: Q1
Fwd Ind
2: Q2 Rev
Cap
3: Q3 Rev
Ind
4: Q4
Fwd Cap
-
0:
Unde ned
Indicates what the power PQ quadrant is at that moment.
VA Quadrant
0:
Unde ned
1: Q1
Fwd
Cap AV
2: Q2 Rev
Ind AV
3: Q3 Rev
Cap VA
4: Q4
Fwd Ind
VA
-
0:Unde ned Indicates what the power VA quadrant is at that moment.
Reset energy
calculators
("Reset 3ph Energies")
0: -
1: Reset
-
0: -
Resets the memory of the three-phase energy calculators.
Goes automatically back to the "-" state after the reset is
nished.
EP per phase
measurement
("EP meas per phase")
0:
Disabled
1:
Enabled
-
0: Disabled
Enables/disables the active energy per phase measurement.
EQ per phase
measurement
("EQ meas per phase")
0:
Disabled
1:
Enabled
-
0: Disabled
Enables/disables the reactive energy per phase measurement.
Per phase energy pre x
("E phs M or k")
0: Mega
1: Kilo
-
0: Mega
De nes whether energy (per phase) is measured with the
pre x 'kilo' (10
3
) or 'mega' (10
6
).
Reset energy
calculators (per phase)
("Reset E per phase")
0: -
1: Reset
-
0: -
Resets the memory of the indivisual phase energy calculator.
Goes automatically back to the "-" state after the reset is
nished.
Table. 5.2.3. - 36. Energy Dose Counter 1 settings
Name
Range
Step
Default
Description
Energy
dose
counter
mode
0: Disabled
1: Activated
-
0: Disabled
Enables/disables energy dose counters generally.
DC 1…4
enable
0: Disabled
1: Enabled
-
0: Disabled
Enables/disables the energy dose counter 1…4
individually.
AQ-E215
Instruction manual
Version: 2.01
© Arcteq Relays Ltd
60
Содержание AQ-E215
Страница 1: ...AQ E215 Energy management IED Instruction manual ...
Страница 4: ...206 11 Contact and reference information AQ E215 Instruction manual Version 2 01 3 Arcteq Relays Ltd ...
Страница 186: ...Figure 8 13 113 Device installation AQ E215 Instruction manual Version 2 01 185 Arcteq Relays Ltd ...
Страница 206: ... Pt100 1000 Balco500 Ni power module AQ E215 Instruction manual Version 2 01 205 Arcteq Relays Ltd ...