Output magnitudes
Input magnitudes
4 × mA output signal (DC)
1 × mA input signal (DC)
mA input
Range (hardware)
Range (measurement)
Inaccuracy
0...33 mA
0...24 mA
±0.1 mA
Update cycle
Response time @ 5 ms cycle
Update cycle time inaccuracy
5...10 000 ms, setting step 5 ms
~ 15 ms (13...18 ms)
Max. +20 ms above the set cycle
mA input scaling range
Output scaling range
0...4000 mA
-1 000 000.0000…1 000 000.0000, setting step 0.0001
mA output
Inaccuracy @ 0...24 mA
±0.01 mA
Response time @ 5 ms cycle [ xed]
< 5 ms
mA output scaling range
Source signal scaling range
0...24 mA, setting step 0.001 mA
-1 000 000.000…1 000 000.0000, setting step 0.0001
9.1.3.4. RTD & mA input module
Table. 9.1.3.4. - 153. Technical data for the RTD & mA input module.
Channels 1-8
2/3/4-wire RTD and thermocouple sensors
Pt100 or Pt1000
Type K, Type J, Type T and Type S
Channels 7 & 8 support mA measurement
Measurement range
mA input range
0…33 mA
9.1.3.5. RS-232 & serial ber communication module
Table. 9.1.3.5. - 154. Technical data for the RS-232 & serial ber communication module.
Ports
RS-232
Serial ber (GG/PP/GP/PG)
Serial port wavelength
660 nm
Cable type
1 mm plastic ber
9.1.3.6. Double LC 100 Mbps Ethernet communication module
Table. 9.1.3.6. - 155. Technical data for the double LC 100 Mbps Ethernet communication module.
Protocols
AQ-E215
Instruction manual
Version: 2.01
© Arcteq Relays Ltd
194
Содержание AQ-E215
Страница 1: ...AQ E215 Energy management IED Instruction manual ...
Страница 4: ...206 11 Contact and reference information AQ E215 Instruction manual Version 2 01 3 Arcteq Relays Ltd ...
Страница 186: ...Figure 8 13 113 Device installation AQ E215 Instruction manual Version 2 01 185 Arcteq Relays Ltd ...
Страница 206: ... Pt100 1000 Balco500 Ni power module AQ E215 Instruction manual Version 2 01 205 Arcteq Relays Ltd ...