Thermal withstand
630 V
RMS
(continuous)
NOTE!
Voltage measurement accuracy has been veri ed with 50/60 Hz.
The amplitude difference is 0.2 % and the angle difference is 0.5 degrees higher at 16.67 Hz and other
frequencies.
9.1.1.3. Power and energy measurement
Table. 9.1.1.3. - 140. Power and energy measurement accuracy
Power measurement P, Q, S
Frequency range 6…75 Hz
Inaccuracy
0.3 % <1.2 × I
N
or 3 VA secondary
1.0 % >1.2 × I
N
or 3 VA secondary
Energy measurement
Frequency range 6…75 Hz
Energy and power metering inaccuracy
IEC 62053-22 class 0.5 S (50/60Hz) as standard
IEC 62053-22 class 0.2 S (50/60Hz) option available (see the order code for details)
Figure. 9.1.1.3. - 115. Energy and power metering accuracy in the optional 0.2 S accuracy model.
AQ-E215
Instruction manual
Version: 2.01
189
© Arcteq Relays Ltd