No scaling
1/10
1/100
1/1000
1/10 000
1/100 000
1/1 000 000
10
100
1000
10 000
100 000
1 000 000
Deadband settings.
Table. 6.1.8. - 131. Analog change deadband settings.
Name
Range
Step
Default
Description
General deadband
0.1…10.0 %
0.1 %
2 %
Determines the general data reporting deadband settings.
Active energy deadband
0.1…1000.0
kWh
0.1
kWh
2 kWh
Determines the data reporting deadband settings for this
measurement.
Reactive
energy deadband
0.1…1000.0
kVar
0.1
kVar
2 kVar
Determines the data reporting deadband settings for this
measurement.
Active power deadband
0.1…1000.0
kW
0.1
kW
2 kW
Determines the data reporting deadband settings for this
measurement.
Reactive power deadband 0.1…1000.0
kVar
0.1
kVar
2 kVar
Determines the data reporting deadband settings for this
measurement.
Apparent
power deadband
0.1…1000.0
kVA
0.1
kVA
2 kVA
Determines the data reporting deadband settings for this
measurement.
Power factor deadband
0.01…0.99
0.01
0.05
Determines the data reporting deadband settings for this
measurement.
Frequency deadband
0.01…1.00 Hz 0.01
Hz
0.1 Hz
Determines the data reporting deadband settings for this
measurement.
Current deadband
0.01…50.00 A 0.01 A 5 A
Determines the data reporting deadband settings for this
measurement.
Residual
current deadband
0.01…50.00 A 0.01 A 0.2 A
Determines the data reporting deadband settings for this
measurement.
Voltage deadband
0.01…
5000.00 V
0.01 V
200 V
Determines the data reporting deadband settings for this
measurement.
Residual
voltage deadband
0.01…
5000.00 V
0.01 V
200 V
Determines the data reporting deadband settings for this
measurement.
Angle
measurement deadband
0.1…5.0 deg
0.1
deg
1 deg
Determines the data reporting deadband settings for this
measurement.
Integration time
0…10 000 ms
1 ms
-
Displays the integration time of the protocol.
6.1.9. SPA
The device can act as a SPA slave. SPA can be selected as the communication protocol for the COM
B port (RS485 port in the CPU module). When the device includes a serial RS-232 card connector, the
SPA protocol can also be selected as the communication protocol for the COM E and COM F ports.
Please refer to the chapter "Construction and installation" in the device manual to see the connections
for these modules.
AQ-E215
Instruction manual
Version: 2.01
© Arcteq Relays Ltd
154
Содержание AQ-E215
Страница 1: ...AQ E215 Energy management IED Instruction manual ...
Страница 4: ...206 11 Contact and reference information AQ E215 Instruction manual Version 2 01 3 Arcteq Relays Ltd ...
Страница 186: ...Figure 8 13 113 Device installation AQ E215 Instruction manual Version 2 01 185 Arcteq Relays Ltd ...
Страница 206: ... Pt100 1000 Balco500 Ni power module AQ E215 Instruction manual Version 2 01 205 Arcteq Relays Ltd ...