9.1.3. Option cards
9.1.3.1. Digital input module
Table. 9.1.3.1. - 150. Technical data for the digital input module.
Rated values
Rated auxiliary voltage
5…265 V (AC/DC)
Current drain
2 mA
Scanning rate
Activation/release delay
5 ms
5...11 ms
Settings
Pick-up threshold
Release threshold
Software settable: 16…200 V, setting step 1 V
Software settable: 10…200 V, setting step 1 V
Pick-up delay
Software settable: 0…1800 s
Drop-off delay
Software settable: 0…1800 s
Polarity
Software settable: Normally On/Normally Off
Terminal block connection
Terminal block
Phoenix Contact MSTB 2,5/5-ST-5,08
Solid or stranded wire
Maximum wire diameter
2.5 mm
2
9.1.3.2. Digital output module
Table. 9.1.3.2. - 151. Technical data for the digital output module.
Rated values
Rated auxiliary voltage
265 V (AC/DC)
Continuous carry
5 A
Make and carry 0.5 s
Make and carry 3 s
30 A
15 A
Breaking capacity, DC (L/R = 40 ms)
at 48 VDC
at 110 VDC
at 220 VDC
1 A
0.4 A
0.2 A
Control rate
5 ms
Settings
Polarity
Software settable: Normally On/Normally Off
Terminal block connection
Terminal block
Phoenix Contact MSTB 2,5/5-ST-5,08
Solid or stranded wire
Maximum wire diameter
2.5 mm
2
9.1.3.3. Milliampere module (mA out & mA in)
Table. 9.1.3.3. - 152. Technical data for the milliampere module.
Signals
AQ-E215
Instruction manual
Version: 2.01
193
© Arcteq Relays Ltd
Содержание AQ-E215
Страница 1: ...AQ E215 Energy management IED Instruction manual ...
Страница 4: ...206 11 Contact and reference information AQ E215 Instruction manual Version 2 01 3 Arcteq Relays Ltd ...
Страница 186: ...Figure 8 13 113 Device installation AQ E215 Instruction manual Version 2 01 185 Arcteq Relays Ltd ...
Страница 206: ... Pt100 1000 Balco500 Ni power module AQ E215 Instruction manual Version 2 01 205 Arcteq Relays Ltd ...