Object set and status
Local/Remote status: control access may be set to Local or Remote (Local by default; please
note that when local control is enabled, the object cannot be controlled through the bus and
vice versa).
Object name: the name of the object (objects are named Object1... Object5 by default).
Object type: selects the type of the object from Grounding disconnector, Motor-controlled
disconnector, Circuit breaker and Withdrawable circuit breaker (Circuit breaker by default).
Object x status: the status can be Bad, Closed, Open and Intermediate. The status
"Intermediate" is the phase between "Open" and "Closed" where both status inputs are 0. The
status "Bad" occurs when both status inputs of the object/cart are 1.
Additional status information: gives feedback from the object on whether the opening and
closing are allowed or blocked, whether the object is ready, and whether the synchronization
status is ok.
Use Synchrocheck & Use Object ready: closing the object is forbidden when the sides are not
synchronized or when the object is not ready to be closed.
Open and close requests: displays the statistics, i.e. the number of Open and Close requests.
Clear statistics: statistics can be cleared by choosing "Clear statistics" and then "Clear".
I/O
An object has Open and Close inputs (connected to physical output relays).
A withdrawable object has In and Out inputs.
Both "Object Ready" and "Synchrocheck" have status inputs.
Status can be indicated by any of the following: digital inputs, logical inputs or outputs, RTDs,
object status information as well as stage status signals (START, TRIP, BLOCKED, etc.).
Operation settings
You can set six (6) separate timeouts for individual objects in the "Settings" section.
After the set delay, if the controlled object does not respond accordingly, the procedure is
terminated and a fail message is issued.
Control settings (DI)
Access level for Mimic control: determines the access level required to control Mimic (each
level has its own password). By default, the access level is set to "Con gurator".
You can use digital inputs to control the object locally or remotely. Remote controlling via the
bus is con gured in the protocol level.
APPLICATION CONTROL
You can connect object statuses directly to physical outputs in the "Signal connections"
subsection (
Control
→
Application control
). They can be connected to output relays, as well as to user-
con gurable LEDs. A connection to an output can be either latched ("|x|") or non-latched ("x").
Object blocking is done in the "Blocking input control" subsection. It can be done by any of the
following: digital inputs, logical inputs or outputs, object status information as well as stage starts, trips
or blocks.
REGISTERS AND EVENTS
You can view the last twelve (12) registers of the control functions and objects through the
"Registers"subsection.
You can view the events speci c to each control function and controlled object through the "Events"
subsection.
AQ-E215
Instruction manual
Version: 2.01
© Arcteq Relays Ltd
16
Содержание AQ-E215
Страница 1: ...AQ E215 Energy management IED Instruction manual ...
Страница 4: ...206 11 Contact and reference information AQ E215 Instruction manual Version 2 01 3 Arcteq Relays Ltd ...
Страница 186: ...Figure 8 13 113 Device installation AQ E215 Instruction manual Version 2 01 185 Arcteq Relays Ltd ...
Страница 206: ... Pt100 1000 Balco500 Ni power module AQ E215 Instruction manual Version 2 01 205 Arcteq Relays Ltd ...