Setting groups
Figure. 4.4. - 7. Setting groups submenu.
The
Setting groups
submenu displays all the information related to setting group changing, such as the
following:
Active setting group: displays the current active setting group (SG1…SG8).
Force SG change: this setting allows the activation of a setting group at will (please note that
Force SG change enable must be "Enabled").
Used setting groups: this setting allows the activation of setting groups SG1...SG8 (only one
group is active by default).
SG local select: selects the local control for the different setting groups (can use digital inputs,
logical inputs or outputs, RTDs, object status information as well as stage starts, trips or
blocks).
SG events: event masking for setting groups (masks are OFF by default; please note that only
masked events appear in the event list).
Setting group 1 (SG1) has the highest priority, while Setting group 8 (SG8) has the lowest priority.
Setting groups can be controlled with pulses or with both pulses and static signals (see the image
below).
Figure. 4.4. - 8. Example of group changing.
AQ-E215
Instruction manual
Version: 2.01
© Arcteq Relays Ltd
14