Module connectors
Table. 8.2. - 135. Module connector descriptions.
Connector
Description
COM A
Communication port A, or the RJ-45 port. Used for the AQtivate setting tool connection and for IEC 61850,
Modbus/TCP, IEC 104, DNP3 and station bus communications.
COM B
Communication port B, or the RS-485 port. Used for the SCADA communications for the following protocols:
Modbus/RTU, Modbus I/O, SPA, DNP3, IEC 101 and IEC 103. The pins have the following designations: Pin 1 =
DATA +, Pin 2 = DATA –, Pin 3 = GND, Pins 4 & 5 = Terminator resistor enabled by shorting.
Model with 3 digital inputs
Model with 2 digital inputs
X 1
Digital input 1, nominal threshold voltage 24 V, 110 V
or 220 V.
Digital input 1, nominal threshold voltage 24 V, 110 V
or 220 V.
X 2
Digital input 2, nominal threshold voltage 24 V, 110 V
or 220 V.
GND for digital input 1.
X 3
Digital input 3, nominal threshold voltage 24 V, 110 V
or 220 V.
Digital input 2, nominal threshold voltage 24 V, 110 V
or 220 V.
X 4
Common GND for digital inputs 1, 2 and 3.
GND for digital input 2.
X 5:6
Output relay 1, with a normally open (NO) contact.
X 7:8
Output relay 2, with a normally open (NO) contact.
X 9:10
Output relay 3, with a normally open (NO) contact.
X 11:12
Output relay 4, with a normally open (NO) contact.
X 13:14:15
Output relay 5, with a changeover contact.
X 16:17:18
System fault's output relay, with a changeover contact. Pins 16 and 17 are closed when the unit has a system
fault or is powered OFF. Pins 16 and 18 are closed when the unit is powered ON and there is no system fault.
X 19:20
Power supply IN. Either 85…265 VAC/DC (model A; order code "H") or 18…75 DC (model B; order code
"L"). Positive side (+) to Pin 20.
GND
The relay's earthing connector.
By default, the CPU module (combining the CPU, the I/O and the power supply) is included in all AQ-
2xx IEDs to provide two standard communication ports and the relay's basic digital I/O. The module
can be ordered to include 2 or 3 digital inputs.
The current consumption of the digital inputs is 2 mA when activated, while the range of the operating
voltage is 24 V/110 V/220 V depending on the ordered hardware. All digital inputs are scannced in 5
ms program cycles, and their pick-up and release delays as well as their NO/NC selection can be set
with software. The digital output controls are also set by the user with software. By default, the digital
outputs are controlled in 5 ms program cycles. All output contacts are mechanical. The rated voltage
of the NO/NC outputs is 250 VAC/DC.
The auxiliary voltage is de ned in the ordering code: the available power supply models available are
A (85…265 VAC/DC) and B (18…75 DC). For further details, please refer to the "Auxiliary voltage"
chapter in the "Technical data" section of this document.
Digital input settings
The settings described in the table below can be found at
Control
→
Device I/O
→
Digital input
settings
in the relay settings.
Table. 8.2. - 136. Digital input settings.
Name
Range
Step Default
Description
AQ-E215
Instruction manual
Version: 2.01
169
© Arcteq Relays Ltd
Содержание AQ-E215
Страница 1: ...AQ E215 Energy management IED Instruction manual ...
Страница 4: ...206 11 Contact and reference information AQ E215 Instruction manual Version 2 01 3 Arcteq Relays Ltd ...
Страница 186: ...Figure 8 13 113 Device installation AQ E215 Instruction manual Version 2 01 185 Arcteq Relays Ltd ...
Страница 206: ... Pt100 1000 Balco500 Ni power module AQ E215 Instruction manual Version 2 01 205 Arcteq Relays Ltd ...