Figure. 4.4. - 16. Device I/O matrix subsection.
Through the Device I/O matrix subsection you can connect digital inputs, logic outputs, protection
stage status signals (START, TRIP, BLOCKED, etc.) and object status signals to output relays, or to
LEDs con gured by the used. A connection can be latched ("|x|") or non-latched ("x"). Please note that
a non-latched output is deactivated immediately when the triggering signal is disabled, while a latched
signal stays active until the triggering signal deactivates and the latched function is cleared.
You can clear latched signals by entering the mimic display and the pressing the Back button on the
panel.
Figure. 4.4. - 17. Programmable control switch subsection.
Programmable control switches (PCSs) are switches that can be used to control signals while in the
mimic view. These signals can be used in a variety of situations, such as for controlling the logic
program, for function blocking, etc. You can name each switch and set the access level to determine
who can control the switch.