Phase current ILx
("Pha.curr.ILx")
0.00…
1250.0 × In
0.01
× In
The fundamental frequency RMS current measurement (in p.u.) from each of the
phase current channels.
Phase current ILx
TRMS
("Pha.curr.ILx
TRMS")
0.00…
1250.0 × In
0.01
× In
The TRMS current (inc. harmonics up to 31
st
) measurement (in p.u.) from each of
the phase current channels.
Peak-to-peak
current ILx
("P-P curr.ILx")
0.00…500.0
× In
0.01
× In
The peak-to-peak current measurement (in p.u.) from each of the phase current
channels.
Table. 5.2.1. - 11. Primary phase current measurements.
Name
Range
Step
Description
Primary phase current
ILx
("Pri.Pha.curr.ILx")
0.00…1 000
000.0 A
0.01
A
The primary fundamental frequency RMS current measurement from each
of the phase current channels.
Primary phase current
ILx TRMS
("Pha.curr.ILx TRMS
Pri")
0.00…1 000
000.0 A
0.01
A
The primary TRMS current (inc. harmonics up to 31
st
) measurement
from each of the phase current channels.
Table. 5.2.1. - 12. Secondary phase current measurements.
Name
Range
Step
Description
Secondary phase
current ILx
("Sec.Pha.curr.ILx")
0.00…
300.0 A
0.01
A
The primary fundamental frequency RMS current measurement from each of
the phase current channels.
Secondary phase
current ILx TRMS
("Pha.curr.ILx TRMS
Sec")
0.00…
300.0 A
0.01
A
The primary TRMS current (inc. harmonics up to 31
st
) measurement
from each of the phase current channels.
Table. 5.2.1. - 13. Phase angle measurements.
Name
Range
Step
Description
Phase angle ILx
("Pha.angle
ILx")
0.00…360.00
deg
0.01
deg
The phase angle measurement from each of the three phase current
inputs.
Table. 5.2.1. - 14. Per-unit residual current measurements.
Name
Range
Step
Description
Residual current I0x
("Res.curr.I0x")
0.00…
1250.0 × In
0.01
× In
The fundamental frequency RMS current measurement (in p.u.) from the
residual current channel I01 or I02.
Calculated I0
("calc.I0")
0.00…
1250.0 × In
0.01
× In
The fundamental frequency RMS current measurement (in p.u.) from the
calculated I0 current channel.
Phase current
I0x TRMS
("Res.curr.I0x TRMS")
0.00…
1250.0 × In
0.01
× In
The TRMS current (inc. harmonics up to 31
st
) measurement (in p.u.) from the
residual current channel I01 or I02.
Peak-to-peak current
I0x
("P-P curr.I0x")
0.00…
500.0 × In
0.01
× In
The peak-to-peak current measurement (in p.u.) from the residual current
channel I01 or I02.
Table. 5.2.1. - 15. Primary residual current measurements.
Name
Range
Step
Description
Primary residual
current I0x
("Pri.Res.curr.I0x")
0.00…1 000
000.0 A
0.01
A
The primary fundamental frequency RMS current measurement from the
residual current channel I01 or I02.
AQ-E215
Instruction manual
Version: 2.01
© Arcteq Relays Ltd
44
Содержание AQ-E215
Страница 1: ...AQ E215 Energy management IED Instruction manual ...
Страница 4: ...206 11 Contact and reference information AQ E215 Instruction manual Version 2 01 3 Arcteq Relays Ltd ...
Страница 186: ...Figure 8 13 113 Device installation AQ E215 Instruction manual Version 2 01 185 Arcteq Relays Ltd ...
Страница 206: ... Pt100 1000 Balco500 Ni power module AQ E215 Instruction manual Version 2 01 205 Arcteq Relays Ltd ...