Figure. 5.5.4. - 72. Activating analog input scaling to create a scaling curve.
Table. 5.5.4. - 96. Main settings (input channel).
Name
Range
Default
Description
Analog input scaling
0: Disabled
1: Activated
0: Disabled
Enables and disables the mA input.
Scaling curve 1...4
0: Disabled
1: Activated
0: Disabled
Enables and disables the scaling curve and the mA input
measurement.
Curve 1...4 input signal
select
0: RTD S1
resistance
…
15: RTD S16
resistance
16: mA in 1 (I card
1)
17: mA in 2 (I card
2)
0: RTD S1
resistance
De nes the measurement category used for mA input
control.
The input signal lter (see the image below) calculates the average of received mA signals according to
the set time constant. This is why rapid changes and disturbances (such as fast spikes) are smothered.
The Nyquist rate states that the lter time constant must be at least double the period time of the
disturbance process signal. For example, the value for the lter time constant is 2 seconds for a 1
second period time of a disturbance oscillation.
When the curve signal is out of range, it activates the "Out of range" alarm, which can be used inside
logic or with other relay functions. The signal can be assigned directly to an output relay or to an LED in
the I/O matrix. The "Out of range" signal is activated, when the measured mA signal falls below the set
input minimum limit, or when it exceeds the input maximum limit. The "Out of range" signal is very
useful when e.g. a 4…20 mA input signal is used (see the image below).
AQ-E215
Instruction manual
Version: 2.01
117
© Arcteq Relays Ltd
Содержание AQ-E215
Страница 1: ...AQ E215 Energy management IED Instruction manual ...
Страница 4: ...206 11 Contact and reference information AQ E215 Instruction manual Version 2 01 3 Arcteq Relays Ltd ...
Страница 186: ...Figure 8 13 113 Device installation AQ E215 Instruction manual Version 2 01 185 Arcteq Relays Ltd ...
Страница 206: ... Pt100 1000 Balco500 Ni power module AQ E215 Instruction manual Version 2 01 205 Arcteq Relays Ltd ...