Figure. 5.2.2. - 40. Connections.
The following table presents the initial data of the connection.
Table. 5.2.2. - 23. Initial data.
Phase voltage VT
- VT primary: 20 000 V
- VT secondary: 100 V
Zero sequence voltage VT
- U4 VT primary: 20 000 V
- U4 VT secondary: 100 V
- the zero sequence voltage is connected similarly to line-to-neutral voltages (+U0).
- in case wiring is incorrect, all polarities can be individually switched by 180 degrees in the relay.
If the protection is voltage-based, the supervised voltage can be based either on line-to-line voltages or
on line-to-earth voltages. This selection is de ned in the "Measured magnitude" of each protection
stage menu separately (
Protection
→
Voltage
→
[protection stage menu]
→
INFO
; see the image
below). The number of available protection functions depends on the relay type.
AQ-E215
Instruction manual
Version: 2.01
© Arcteq Relays Ltd
48