Pickup settings:
- Voltage (low pick-up)
- Voltage (high pick-up)
- Angle shift limit
0.05…0.50 × U
N
, setting step 0.01 × U
N
0.50…1.10 × U
N
, setting step 0.01 × U
N
2.00…90.00 deg, setting step 0.10 deg
Inaccuracy:
- Voltage
- U angle (U> 1 V)
±1.5 %U
SET
±1.5°
External line/bus side pick-up (optional)
0
→
1
Time delay for alarm
De nite time function operating time setting
0.00…1800.00 s, setting step 0.005 s
Inaccuracy:
- De nite time (U
M
/U
SET
ratio > 1.05/0.95)
±1.0 % or ±35 ms
Instant operation time (alarm):
- U
M
/U
SET
ratio > 1.05/0.95
<80 ms
VTS MCB trip bus/line (external input)
<50 ms
Reset
Reset ratio
97/103 % of the pick-up voltage setting
Reset time setting
Inaccuracy: Reset time
0.010…10.000 s, step 0.005 s
±2.0 % or ±80 ms
Instant reset time and start-up reset
<50 ms
VTS MCB trip bus/line (external input)
<50 ms
Note!
When turning on the auxiliary power of an IED, the normal condition of a stage has to be ful lled
before tripping.
9.2.3.2. Disturbance recorder
Table. 9.2.3.2. - 167. Technical data for the disturbance recorder function.
Recorded values
Recorder analogue
channels
0…20 channels
Freely selectable
Recorder digital channels
0…95 channels
Freely selectable analogue and binary signals
5 ms sample rate (FFT)
Performance
Sample rate
8, 16, 32 or 64 samples/cycle
Recording length
0.000…1800.000 s, setting step 0.001 s
The maximum length is determined by the chosen signals.
Number of recordings
0…100, 60 MB of shared flash memory reserved
The maximum number of recordings according to the chosen signals and operation time setting
combined
9.2.3.3. Total harmonic distortion (THD)
Table. 9.2.3.3. - 168. Technical data for the total harmonic distortion function.
Input signals
Current input magnitudes
Current measurement channels (FFT result) up to the 31
st
harmonic
component.
AQ-E215
Instruction manual
Version: 2.01
© Arcteq Relays Ltd
200
Содержание AQ-E215
Страница 1: ...AQ E215 Energy management IED Instruction manual ...
Страница 4: ...206 11 Contact and reference information AQ E215 Instruction manual Version 2 01 3 Arcteq Relays Ltd ...
Страница 186: ...Figure 8 13 113 Device installation AQ E215 Instruction manual Version 2 01 185 Arcteq Relays Ltd ...
Страница 206: ... Pt100 1000 Balco500 Ni power module AQ E215 Instruction manual Version 2 01 205 Arcteq Relays Ltd ...