Phases L2 (B) and L3 (C) have switched places (network rotation wrong).
Phase currents
IL1: 1.00 × In / 0.00 deg
IL2: 1.00 × In / 120.00 deg
IL3: 1.00 × In / 240.00 deg
Sequence currents
I1: 0.00 × In / 0.00 deg
I2: 1.00 × In / 0.00 deg
I0Calc: 0.00 × In / 0.00 deg
Resolution:
- switch the wires between the connectors 3 and 5 in the CT module
Phases L3 (C) and L1 (A) have switched places (network rotation wrong).
Phase currents
IL1: 1.00 × In / 0.00 deg
IL2: 1.00 × In / 120.00 deg
IL3: 1.00 × In / 240.00 deg
Sequence currents
I1: 0.00 × In / 0.00 deg
I2: 1.00 × In / 0.00 deg
I0Calc: 0.00 × In / 0.00 deg
Resolution:
- switch the wires between the connectors 1 and 5 in the CT module
Settings
Table. 5.2.1. - 7. Settings of the Phase CT scaling.
Name
Range
Step Default
Description
Scale
meas. to
In
0: CT
nom
p.u.
1:
Object
In p.u.
-
0: CT
nom
p.u.
The selection of the reference used in the relay's per-unit system scaling. Either the
set phase current CT primary or the protected object's nominal current.
Phase CT
primary
1…25
000.000
A
0.001
A
100.000
A
The rated primary current of the current transformer.
Phase CT
secondary
0.200…
10.000
A
0.001
A
5.000 A
The rated secondary current of the current transformer.
Nominal
current In
1…25
000.000
A
0.001
A
100.000
A
The nominal current of the protected object. This setting is only visible if the option
"Object In p.u." has been selected in the "Scale meas. to In" setting.
AQ-E215
Instruction manual
Version: 2.01
© Arcteq Relays Ltd
42
Содержание AQ-E215
Страница 1: ...AQ E215 Energy management IED Instruction manual ...
Страница 4: ...206 11 Contact and reference information AQ E215 Instruction manual Version 2 01 3 Arcteq Relays Ltd ...
Страница 186: ...Figure 8 13 113 Device installation AQ E215 Instruction manual Version 2 01 185 Arcteq Relays Ltd ...
Страница 206: ... Pt100 1000 Balco500 Ni power module AQ E215 Instruction manual Version 2 01 205 Arcteq Relays Ltd ...