Thermal withstand
25 A (continuous)
100 A (for 10 s)
500 A (for 1 s)
1250 A (for 0.01 s)
Frequency measurement range
From 6…75 Hz fundamental, up to the 31
st
harmonic current
Current measurement range
1 mA…75 A (RMS)
Current measurement inaccuracy
0.002…25.000 × I
N
< ±0.5 % or < ±0.6 mA
25…375 × I
N
< ±1.0 %
Angle measurement inaccuracy
< ±0.2° (I> 0.01 A)
< ±1.0° (I
≤
0.01 A)
Burden (50/60Hz)
<0.1 VA
Transient overreach
<5 %
Terminal block connection
Terminal block
Phoenix Contact FRONT 4-H-6,35
Solid or stranded wire
Maximum wire diameter
4 mm
2
NOTE!
Current measurement accuracy has been veri ed with 50/60 Hz.
The amplitude difference is 0.2 % and the angle difference is 0.5 degrees higher at 16.67 Hz and other
frequencies.
9.1.1.2. Voltage measurement
Table. 9.1.1.2. - 139. Technical data for the voltage measurement module.
Connection
Measurement channels/VT inputs
4 independent VT inputs (Ua, Ub, Uc and Ud)
Measurement
Voltage measuring range
0.50…480.00 V (RMS)
Voltage measurement inaccuracy
1…2 V ±1.5 %
2…10 V ±0.5 %
10…480 V ±0.35 %
Angle measurement inaccuracy
±0.2 degrees (15…300 V)
±1.5 degrees (1…15 V)
Voltage measurement bandwidth (freq.)
7…75 Hz fundamental, up to the 31
st
harmonic voltage
Terminal block connection
Terminal block
Phoenix Contact PC 5/8-STCL1-7.62
Solid or stranded wire
Maximum wire diameter
6 mm
2
Input impedance
24.5…24.6 Ω
Burder (50/60 Hz)
<0.02 VA
AQ-E215
Instruction manual
Version: 2.01
© Arcteq Relays Ltd
188
Содержание AQ-E215
Страница 1: ...AQ E215 Energy management IED Instruction manual ...
Страница 4: ...206 11 Contact and reference information AQ E215 Instruction manual Version 2 01 3 Arcteq Relays Ltd ...
Страница 186: ...Figure 8 13 113 Device installation AQ E215 Instruction manual Version 2 01 185 Arcteq Relays Ltd ...
Страница 206: ... Pt100 1000 Balco500 Ni power module AQ E215 Instruction manual Version 2 01 205 Arcteq Relays Ltd ...