There are up to 64 GOOSE inputs available for use. Each of the GOOSE inputs also has a
corresponding input quality signal which can also be used in internal logic. The quality is good, when
the input quality is low (that is, when the quality is marked as "0"). The value of the input quality can
increase as a result of a GOOSE time-out or a con guration error, for example. The status and quality
of the various logical input signals can be viewed at the
GOOSE IN status
and
GOOSE IN quality
tabs
at
Control
→
Device I/O
→
Logical signals
.
GOOSE input settings
The table below presents the different settings available for all 64 GOOSE inputs.
Table. 6.1.5. - 125. GOOSE input settings.
Name
Range
Step Default
Description
In use
0: No
1: Yes
-
0: No
Enables and disables the GOOSE input in question.
Application ID
("AppID")
0×0…
0×3FFF
0×1
0×0
De nes the application ID that will be matched with the publisher's GOOSE
control block.
Con guration
revision
("ConfRev")
1…2
32
-1
1
1
De nes the con guration revision that will be matched with the publisher's
GOOSE control block.
Data index
("DataIdx")
0…99
1
-
De nes the data index of the value in the matched published frame. It is the
status of the GOOSE input.
NextIdx is
quality
0: No
1: Yes
-
0: No
Selects whether or not the next received input is the quality bit of
the GOOSE input.
Data type
0: Boolean
1: Integer
2:
Unsigned
3: Floating
point
-
0:
Boolean Selects the data type of the GOOSE input.
Setting the publisher
The con guration of the GOOSE publisher is done using the IEC 61850 tool in AQtivate (
Tools
→
Communication
→
IEC 61850
). In order for the GOOSE publishing service to be used, both of the
GCBs and the GOOSE data sets must be set.
The GOOSE control blocks are accessed by clicking the sixth icon on the main toolbar,
"Con gurations" (see the image below).
The GOOSE control block settings are located on the right side of the Con gurations pop-up window
(see the image below). Both GCB1 and GCB 2 must be set. The important parameters are "App
ID" (should be unique for the system) and "ConfRev" (checked by the subscriber). If VLAN switches
have been used to build the sub-networks, both the "VLAN priority" and the "VLAN ID" parameters must
be set to match the system speci cations.
AQ-E215
Instruction manual
Version: 2.01
149
© Arcteq Relays Ltd
Содержание AQ-E215
Страница 1: ...AQ E215 Energy management IED Instruction manual ...
Страница 4: ...206 11 Contact and reference information AQ E215 Instruction manual Version 2 01 3 Arcteq Relays Ltd ...
Страница 186: ...Figure 8 13 113 Device installation AQ E215 Instruction manual Version 2 01 185 Arcteq Relays Ltd ...
Страница 206: ... Pt100 1000 Balco500 Ni power module AQ E215 Instruction manual Version 2 01 205 Arcteq Relays Ltd ...